S-95 (Supervision of Fire Alarm Systems)
QUESTIONS AND ANSWERS RATED A.
AN APPROVED CENTRAL STATION COMPANY IS ONE THAT HAS BEEN
ISSUED A VALID CERTIFICATE FROM ____________.
FDNY
____________ DETECTORS ARE USED TO PROTECT LARGE AREAS. IT IS A
LIGHT BEAM BROKEN BY COMBUSTIBLE PARTICLES.
BEAM
___________ DETECTORS SHUT DOWN A BUILDINGS HVAC SYSTEM AND
RE-DIRECT AIRFLOW.
DUST SMOKE
FIRE ALARM DEVICES SHALL BE PROTECTED, ESPECIALLY DURING
___________.
INSTALLATION
FOR AIR SAMPLING TYPE DETECTORS, THE MAXIMUM AIR SAMPLING
TRANSPORT TIME FROM THE FARTHES POINT SHALL NOT EXCEED
____________.
120 SECONDS
AIR-SAMPLING DETECTORS SHALL GIVE A ____________ SIGNAL IF THE
AIRFLOW IS OUTSIDE THE MANUFACURERS SPECIFIED RANGE.
TROUBLE
MAXIMUM ALLOWABLE TIME FOR FIRE ALARM OUTPUT FUNCTIONS TO
OPERATE ONCE A SMOKE DETECTOR HAS BEEN ACTIVATED IS
__________ SECONDS.
, 10
__________ HEAT DETECTORS DO NOT HAVE TO BE REPLACED AFTER IT
HAS ACTIVATED THE FIRE ALARM.
RATE OF RISE
________ HEAT DETECTORS ACTIVATE THE ALARM WHEN THE DETECTOR
COMPONENTS MELT AT A PRESET TEMPERATURE.
FIXED-TEMPERATURE HEAT DETECTORS
__________ HEAT DETECTORS ARE THE MOST COMMONLY USED.
FIXED-TEMPERATURE
___________ DETECTORS ARE REQUIRED IN ANY BUILDING THAT HAS
FOSSIL FUEL BURNING EQUIPMENT.
CARBON MONOXIDE
THE _________ SHALL ONLY BE RESET AT THE DIRECTION OF A FIRE
DEPARTMENT REPRESENTATIVE.
FIRE ALARM CONTROL PANEL
SINGLE ACTION STATIONS ARE USUALLY FOUND __________.
INDOORS
ONCE ACTIVATED, THE FIRE ALARM SYSTEM CANNOT BE RE-SET AT THE
_____________.
FIRE ALARM MANUAL PULL STATION
A MASTER PLUMBER WITH AN S-12 COF IS ALLOWED TO PERFORM
MAINTENANCE ON SPRINKLER SYSTEMS IN RESIDENTIAL
OCCUPANCIES WITH LESS THAN ____________ SPRINKLERS.
30
QUESTIONS AND ANSWERS RATED A.
AN APPROVED CENTRAL STATION COMPANY IS ONE THAT HAS BEEN
ISSUED A VALID CERTIFICATE FROM ____________.
FDNY
____________ DETECTORS ARE USED TO PROTECT LARGE AREAS. IT IS A
LIGHT BEAM BROKEN BY COMBUSTIBLE PARTICLES.
BEAM
___________ DETECTORS SHUT DOWN A BUILDINGS HVAC SYSTEM AND
RE-DIRECT AIRFLOW.
DUST SMOKE
FIRE ALARM DEVICES SHALL BE PROTECTED, ESPECIALLY DURING
___________.
INSTALLATION
FOR AIR SAMPLING TYPE DETECTORS, THE MAXIMUM AIR SAMPLING
TRANSPORT TIME FROM THE FARTHES POINT SHALL NOT EXCEED
____________.
120 SECONDS
AIR-SAMPLING DETECTORS SHALL GIVE A ____________ SIGNAL IF THE
AIRFLOW IS OUTSIDE THE MANUFACURERS SPECIFIED RANGE.
TROUBLE
MAXIMUM ALLOWABLE TIME FOR FIRE ALARM OUTPUT FUNCTIONS TO
OPERATE ONCE A SMOKE DETECTOR HAS BEEN ACTIVATED IS
__________ SECONDS.
, 10
__________ HEAT DETECTORS DO NOT HAVE TO BE REPLACED AFTER IT
HAS ACTIVATED THE FIRE ALARM.
RATE OF RISE
________ HEAT DETECTORS ACTIVATE THE ALARM WHEN THE DETECTOR
COMPONENTS MELT AT A PRESET TEMPERATURE.
FIXED-TEMPERATURE HEAT DETECTORS
__________ HEAT DETECTORS ARE THE MOST COMMONLY USED.
FIXED-TEMPERATURE
___________ DETECTORS ARE REQUIRED IN ANY BUILDING THAT HAS
FOSSIL FUEL BURNING EQUIPMENT.
CARBON MONOXIDE
THE _________ SHALL ONLY BE RESET AT THE DIRECTION OF A FIRE
DEPARTMENT REPRESENTATIVE.
FIRE ALARM CONTROL PANEL
SINGLE ACTION STATIONS ARE USUALLY FOUND __________.
INDOORS
ONCE ACTIVATED, THE FIRE ALARM SYSTEM CANNOT BE RE-SET AT THE
_____________.
FIRE ALARM MANUAL PULL STATION
A MASTER PLUMBER WITH AN S-12 COF IS ALLOWED TO PERFORM
MAINTENANCE ON SPRINKLER SYSTEMS IN RESIDENTIAL
OCCUPANCIES WITH LESS THAN ____________ SPRINKLERS.
30