Which of the following is not considered "hanging hardware"?
. nozzle
a
b. swivel
c. whip hose
d. shear valve
d. shear valve
er Executive Order. VR-201-E, if the dispensing vacuum of the Healy VP-1000 pump
P
is below __?__ inches of WC, the dispenser should be removed from service.
. 50
A
B. 60
C. 75
D. 100
B. 60
In a coaxial hose for a balance system, the product flows through the ____?
. the below
A
B. the inner hose
C. the outer hose
D. both hoses
B. the inner hose
er the Vapor Recovery Equipment Defects List (VRED), the ____ of any component
P
required to be used by the system's EO. Is not considered a defect.
. absence
A
B. proper installation
, . disconnection
C
D. improper installation
B. proper installation
The three elements in a fire triangle are ____?
. oxygen, fuel, & LEL
A
B. fuel, fire, & carbon dioxide
C. fuel, oxygen, & ignition source
D. ignition source, carbon dioxide, & fuel
C. fuel, oxygen, & ignition source
According to PEI RP-300, a combustible gas indicator is used to?
. determine carbon dioxide levels
A
B. monitor benzene, toluene, & ethyl benzene levels
C. determine the (UEL) upper explosion limit of gasoline
D. detect vapour leaks in the vapour recovery system
D. detect vapour leaks in the vapour recovery system
er CP-201, liquid traps in the dispenser vapour piping are:?
P
A. Not allowed
B. Allowed only with an assist system
C. Allowed if approved by CARB
D. Allowed when hoses with liquid removal systems are used
E. detect vapour leaks in the vapour recovery system
A. Not allowed
Which of the following is not an overfill device?
. ball-float
A
B. spill-bucket
C. tank overfill alarm
D. drop-tube flapper valve
B. spill-bucket
Piping should have a minimum and maximum slope of ____ inch.
. 1/16"-1/8"
A
B. 1/8"-1/4"