LOW VOLTAGE PRACTICE TEST 2 EXAMS ll ll ll l ll ll
1. Class 2 and 3 circuit conductors shall be installed in rigid metal conduit
ll ll ll ll ll ll ll ll ll ll ll ll
a. in hoistways
ll
b. in enclosures
ll
c. under carpets ll
d. in one and two family dwellings: a. in hoistways
ll ll ll ll ll l l ll
Article 725.136(H)
ll
2. Conductors for 24V lighting systems that are extended through a wall are
ll ll ll ll ll ll ll ll ll ll ll
supplied by
ll l l
a. Class 1 power sources ll ll ll
b. Class 2 power sources ll ll ll
c. Class 3 power sources ll ll ll
d. PLTC power sources: b. Class 2 power sources
ll ll l l ll ll ll
Article 411.5(A)(2)
ll
3. Network-powered broadband communications cables and Class 1 cables are ll ll ll ll ll ll ll ll
a. Permitted in the same cable tray ll ll ll ll ll
b. Permitted in the same cable tray with a permanent barrier ll ll ll ll ll ll ll ll ll
c. Not permitted in the same cable tray
ll ll ll ll ll ll
d. band c: d. band c ll l l ll
Article 830.133(A)(1)(E)
ll
4. Optical fiber cables shall be permitted to be installed in the
ll ll ll ll ll ll ll ll ll ll
following raceways
ll l l
a. Any raceway recognized in Ch 3
ll ll ll ll ll
b. Communications raceways ll
c. Innerducts for optical fiber cables ll ll ll ll
d. all of these: d. all of these
ll ll l l ll ll
Article 770.110 (A), (1), (2) and (3)
ll ll ll ll ll ll
5. Uninterruptible power supplies in information technology rooms shall have l l ll ll ll ll ll ll
a. an approved means of disconnecting the output circuits
ll ll ll ll ll ll ll
1/ l1 2
, b. an approved means of disconnecting the supply power
ll ll ll ll ll ll ll
2/ l1 2
1. Class 2 and 3 circuit conductors shall be installed in rigid metal conduit
ll ll ll ll ll ll ll ll ll ll ll ll
a. in hoistways
ll
b. in enclosures
ll
c. under carpets ll
d. in one and two family dwellings: a. in hoistways
ll ll ll ll ll l l ll
Article 725.136(H)
ll
2. Conductors for 24V lighting systems that are extended through a wall are
ll ll ll ll ll ll ll ll ll ll ll
supplied by
ll l l
a. Class 1 power sources ll ll ll
b. Class 2 power sources ll ll ll
c. Class 3 power sources ll ll ll
d. PLTC power sources: b. Class 2 power sources
ll ll l l ll ll ll
Article 411.5(A)(2)
ll
3. Network-powered broadband communications cables and Class 1 cables are ll ll ll ll ll ll ll ll
a. Permitted in the same cable tray ll ll ll ll ll
b. Permitted in the same cable tray with a permanent barrier ll ll ll ll ll ll ll ll ll
c. Not permitted in the same cable tray
ll ll ll ll ll ll
d. band c: d. band c ll l l ll
Article 830.133(A)(1)(E)
ll
4. Optical fiber cables shall be permitted to be installed in the
ll ll ll ll ll ll ll ll ll ll
following raceways
ll l l
a. Any raceway recognized in Ch 3
ll ll ll ll ll
b. Communications raceways ll
c. Innerducts for optical fiber cables ll ll ll ll
d. all of these: d. all of these
ll ll l l ll ll
Article 770.110 (A), (1), (2) and (3)
ll ll ll ll ll ll
5. Uninterruptible power supplies in information technology rooms shall have l l ll ll ll ll ll ll
a. an approved means of disconnecting the output circuits
ll ll ll ll ll ll ll
1/ l1 2
, b. an approved means of disconnecting the supply power
ll ll ll ll ll ll ll
2/ l1 2