R-22 vapor line diameters and lengths are typically specified for a vapor pressure drop that does not
exceed what value? - CORRECT ANSWER d. 6-7 psi or 6 degrees F
Which of the following is a primary consideration when bending soft copper tubing into a bend of any
radius? - CORRECT ANSWER the cross-sectional area of the tube must
not be significantly reduced
The water that results from a defrost cycle of an air to air heat pump (run off) must drain off and away
from the outdoor coil. What can happen if the defrost runoff is not properly drained away? - CORRECT
ANSWER excessive ice can build up on the bottom of the coil and reduce capacity
The component used to reduce sound transmission and prevent water leaks of a packaged heat pump -
CORRECT ANSWER curb gasket
To more accurately sense the refrigerant temperature of horizontal suction lines that are 11/8" or
larger, a thermostatic expansion valve sensing bulb should be mounted at which of the following
positions? - CORRECT ANSWER 4 or 8 o'clock
In order for an evacuation to be considered complete, a heat pump refrigerant circuit should be
evacuated to a vacuum pressure of: - CORRECT ANSWER C. 500 microns
When first inspecting a system known to be leaking, the technician should look for: - CORRECT ANSWER
d. traces of oil
Which of the following measurements are needed to determine low side superheat? - CORRECT
ANSWER d. suction pressure and suction line pressure temperature
, Drive slips are typically installed where, on rectangular duct? - CORRECT ANSWER d. on the shorter
sides
To properly set a heat anticipator it is necessary to check the: - CORRECT ANSWER b. heating control
circuit amperage draw
Using a voltmeter, how does the technician determine voltage drop on the outdoor unit of a heat
pump? - CORRECT ANSWER d. with the outdoor unit not operating and
then with the outdoor unit operating.
What is the smallest refrigerant leak that an electronic leak detector should be capable of sensing? -
CORRECT ANSWER b. 5 oz per year
When checking the pressures in an operating system with a manifold gauge set, refrigerant oil in a hose
will - CORRECT ANSWER c. have no effect on the gauge reading
Which of the following is used to measure air pressure? - CORRECT ANSWER d. diaphragm type
differential pressure
gauge
A residential supply diffuser that is noisy because of a loose van is best serviced by: - CORRECT ANSWER
d. replacing the diffuser
When performing preventive maintenance on a heat pump the technician should check the outdoor fan
to be certain - CORRECT ANSWER c: the fan runs freely with no binding
What is the effect of 170 volts supplied to a 208/230 volt compressor? - CORRECT ANSWER c. current
increases and the motor may trip
On a service call for a cooling problem with a heat pump, your inspections find a liquid line that has
condensation on it. What is the most likely cause? - CORRECT ANSWER b. liquid line is restricted