Code) questions with verified answers
16.01.) With reference to specific minimum requirements for refrigerant pipe and
tubing, one of the following is most nearly correct? Ans✓✓-Standard I.P.S.
copper, brass pipe and tubing shall not be less than 80% copper (ask professor)
16.02.) How many stop valves are required by code in a system using 60 lbs. of
"group one" refrigerant, and having two compressors and two receivers? Ans✓✓-
Four (ask professor)
16.03.) Which of the following ASHRAE "designation and safety classification of
refrigerants" indicate the lowest level of flammability? Ans✓✓-B1
16.04.) A sign on the wall of a refrigerant plant contains pertinent information.
Which of the following can be omitted? Ans✓✓-Number of condensers
16.05.) Which of the following refers to a class "T" machine room? Ans✓✓-All
pipes must be sealed into the wall, ceiling, and floor (ask professor)
16.06.) A soldered joint is a gas tight joint obtained by the joining of metal parts
with metallic mixtures of alloys that melt at temperatures below? Ans✓✓-1000
degrees F and above 400 degrees F
16.07.) If a system contained 400 pounds of a group 2 refrigerant, the number of
required breathing service masks is? Ans✓✓-One
, 16.08.) According to the NYC code, all pipes passing overhead should be a
minimum of how many feet above the floor? Ans✓✓-7.5 feet
16.09.) The NYC code states that the maximum setting of a system's pressure
limiting device should be adjusted to a percentage of the relief valve setting or the
high-side working pressure. The percentage is? Ans✓✓-90%
16.10.) A refrigeration system contains 2000 pounds of refrigerant. The fan used
to exhaust the room in the event of a refrigerant leak should have a capacity of?
Ans✓✓-2900 cfm
16.11.) The charging valve of a 50 ton plant should be located? Ans✓✓-On the
low pressure side
16.12.) A refrigeration system contains 600 pounds of refrigerant. The fan used to
exhaust the room in the event of a refrigerant leak should have a capacity of?
Ans✓✓-1450
16.13.) A specification calls for the installation of a unit air conditioning system in
the lobby of a building. The unit contains 30 pounds of R-12. In keeping with the
code it can be said that? Ans✓✓-It may be installed
16.14.) Sweat joints in copper tubing used for a group 2 refrigerant shall be?
Ans✓✓-Brazed
16.15.) Which refrigeration component does the pressure limiting device control?
Ans✓✓-compressor (ask professor)