Inspect & Test Fire Alarm NICET 2 Exam Questions and Correct Answers Latest Update 2025 Light sources used for testing sensitivity on radiant energy detectors must meet which of the following requirements? - Answers 1) Measured Energy Output 2) Defined distance for testing. Air sampling detectors are required to be tested? - Answers Annually A 25% increase in port pressure is acceptable? - Answers False. An increase of that amount indicates a major change or problem. In air sampling detection systems a decrease in smoke transport times would be acceptable? - Answers False. Test valves should be closed to the valves measured during commissioning. Air Sampling detectors are required to be inspected? - Answers Semiannually Radiant Energy Detectors must be tested - Answers Semiannually Two Way emergency Communication systems must be tested? - Answers Annually True or False? You must scan the disk storage for bad sectors as a requirement for testing of the control unit for a Mass Notification System? - Answers FALSE True or False? You must Power down the unit and restart it when testing the control unit for a Mass Notification System? - Answers TRUE True or False? You must delete unneeded log and error files as par of the required testing for the control unit of Mass Notification Systems? - Answers TRUE True or False? When testing the control unit of a Mass Notification System; verify any remote control software loaded into the system is disabled to prevent unauthorized access. - Answers TRUE Which is NOT a form of Emergency Communication System; 1) Fire fighters Phone 2) Mass notification System 3) One way communication system 4) Audible Zone Alert - Answers Audible Zone Alert Radiant Energy Detectors must be inspected? - Answers Quarterly When testing a Mass Notification system, during the test of the main power supply, you must first ________________ the secondary power supply and test under maximum load. - Answers disconnect Gasoline fires generate energy in which spectrum(s) - Answers 1) UV 2) IR 3) Visible True or False? The only inspection task for radiant energy detectors is to verify no point requiring detection is outside of the detector's field of view? - Answers FALSE In order to test an air sampling detector system ___________________. - Answers the end sampling port on each pipe must be tested. Mass Notification Systems must be tested how often/ - Answers Annually The Low Air pressure switch for a dry pipe sprinkler system must be tested ___________________ - Answers Annually To test the waterflow alarm on a dry pipe sprinkler system ________________ - Answers Open the alarm by-pass valve Which section of NFPA 72 table 143.4.3.2 defines the requirements for testing a two-way communication system AREA OF REFUGE? - Answers Sub section 25 [Table 14.4.3.2 (25)] Which must be tested on an ECS system amplifier? 1) Output Power 2) Backup switching 3) Sound levels 4) Batteries - Answers Backup switching & Batteries True of False? All emergency communication systems require sound pressure level testing per ANSI S1.4a. - Answers FALSE. Only Mass Notification Systems require sound pressure level testing. What requirements for annual testing of the visible appliances on a Mass Notification System? - Answers A) Location of appliances matches approved layout B) Testing per manufacturers instructions C) Candela rating of the bulb To testing the waterflow alarm on a wet pipe sprinkler system - Answers open the valve at the ITV (inspectors test valve). The waterflow alarm must be initiated within __________________ after the water begins to flow. - Answers 90 seconds. A room temperature switch for a sprinkler system shall initiate a signal at _________ degrees fahrenheit. - Answers 40 degrees

Voorbeeld van de inhoud

Inspect & Test Fire Alarm NICET 2 Exam Questions and Correct Answers Latest Update 2025

Light sources used for testing sensitivity on radiant energy detectors must meet which of the following
requirements? - Answers 1) Measured Energy Output

2) Defined distance for testing.

Air sampling detectors are required to be tested? - Answers Annually

A 25% increase in port pressure is acceptable? - Answers False. An increase of that amount indicates a
major change or problem.

In air sampling detection systems a decrease in smoke transport times would be acceptable? - Answers
False. Test valves should be closed to the valves measured during commissioning.

Air Sampling detectors are required to be inspected? - Answers Semiannually

Radiant Energy Detectors must be tested - Answers Semiannually

Two Way emergency Communication systems must be tested? - Answers Annually

True or False? You must scan the disk storage for bad sectors as a requirement for testing of the control
unit for a Mass Notification System? - Answers FALSE

True or False? You must Power down the unit and restart it when testing the control unit for a Mass
Notification System? - Answers TRUE

True or False? You must delete unneeded log and error files as par of the required testing for the control
unit of Mass Notification Systems? - Answers TRUE

True or False? When testing the control unit of a Mass Notification System; verify any remote control
software loaded into the system is disabled to prevent unauthorized access. - Answers TRUE

Which is NOT a form of Emergency Communication System;

1) Fire fighters Phone

2) Mass notification System

3) One way communication system

4) Audible Zone Alert - Answers Audible Zone Alert

Radiant Energy Detectors must be inspected? - Answers Quarterly

When testing a Mass Notification system, during the test of the main power supply, you must first
________________ the secondary power supply and test under maximum load. - Answers disconnect

Gasoline fires generate energy in which spectrum(s) - Answers 1) UV

, 2) IR

3) Visible

True or False? The only inspection task for radiant energy detectors is to verify no point requiring
detection is outside of the detector's field of view? - Answers FALSE

In order to test an air sampling detector system ___________________. - Answers the end sampling
port on each pipe must be tested.

Mass Notification Systems must be tested how often/ - Answers Annually

The Low Air pressure switch for a dry pipe sprinkler system must be tested ___________________ -
Answers Annually

To test the waterflow alarm on a dry pipe sprinkler system ________________ - Answers Open the
alarm by-pass valve

Which section of NFPA 72 table 143.4.3.2 defines the requirements for testing a two-way
communication system AREA OF REFUGE? - Answers Sub section 25 [Table 14.4.3.2 (25)]

Which must be tested on an ECS system amplifier?

1) Output Power

2) Backup switching

3) Sound levels

4) Batteries - Answers Backup switching & Batteries

True of False?

All emergency communication systems require sound pressure level testing per ANSI S1.4a. - Answers
FALSE. Only Mass Notification Systems require sound pressure level testing.

What requirements for annual testing of the visible appliances on a Mass Notification System? - Answers
A) Location of appliances matches approved layout

B) Testing per manufacturers instructions

C) Candela rating of the bulb

To testing the waterflow alarm on a wet pipe sprinkler system - Answers open the valve at the ITV
(inspectors test valve).

The waterflow alarm must be initiated within __________________ after the water begins to flow. -
Answers 90 seconds.

Documentinformatie

Geüpload op
22 januari 2025
Aantal pagina's
8
Geschreven in
2024/2025
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden
$9.99

Verkeerd document? Gratis ruilen Binnen 14 dagen na aankoop en voor het downloaden kan je een ander document kiezen. Je kan het bedrag gewoon opnieuw besteden.
Geschreven door studenten die geslaagd zijn
Direct beschikbaar na je betaling
Online lezen of als PDF

Seller avatar
De reputatie van een verkoper is gebaseerd op het aantal documenten dat iemand tegen betaling verkocht heeft en de beoordelingen die voor die items ontvangen zijn. Er zijn drie niveau’s te onderscheiden: brons, zilver en goud. Hoe beter de reputatie, hoe meer de kwaliteit van zijn of haar werk te vertrouwen is.
TutorJosh
3.5
(75)
Verkocht
491
Volgers
16
Items
32822
Laatst verkocht
2 dagen geleden




Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via Bancontact, iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo eenvoudig kan het zijn.”

Alisha Student

Bezig met je bronvermelding?

Maak nauwkeurige citaten in APA, MLA en Harvard met onze gratis bronnengenerator.

Bezig met je bronvermelding?

Veelgestelde vragen