Permit to install an oil burner is issued by the? - ANSWER - State Fire Marshall
Draft measurements are taken in what? - ANSWER - Inches of water column
Pressure Relief for a Hot Water Boiler is? - ANSWER - 30 Psi
Pressure Relief for a Steam Boiler is? - ANSWER - 15 Psi
How many cubic feet of Air is required for a 1 gallon nozzle? - ANSWER - 1,400
If a power vent fails to start or shuts down during operation, will this affect the burner?
Yes? Or No? - ANSWER - Yes
A Hot Water Boiler needs a low water cut off if over 300,000 B.T.U's? - ANSWER -
False
What is the proper draft setting for an oil burner? - ANSWER - .02 Inches WC
Taco Zones Valves draw .9 Amps? True? Or False? - ANSWER - True
An oil burner tank must be how many feet minimum from an oil burner? - ANSWER - 5
Feet Minimum
What is the gauge thickness for a 220 Gallon tank? - ANSWER - 12 Gauge
What is a good cad cell reading in the light? - ANSWER - 300 -1,000
What is a good cad cell reading in the dark? - ANSWER - 100,000
What device sees flame failure and causes it to lockout? - ANSWER - Cad Cell
A boiler has been flooded by recent rain. What would be the most common problem for
a burner as a result - ANSWER - Electrical damage
What is the minimum size of pipping for copper and black pipe in a residential
installation? - ANSWER - 3/8 unless over 100 ft
If you increased the air on a burner what would happen to the Co2 Reading? -
ANSWER - It would go down