SYSTEMS, S12 sprinkler test
R
U
LA
C
O
D
,THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - ANS OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A
MIN. OF __________ YEARS. - ANS 3
R
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - ANS IMPAIRMENT COORDINATOR
U
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - ANS 1
LA
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - ANS 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. - ANS 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY
C
REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - ANS OWNER OF
THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS
O
OR IT WILL BE CONSIDERED AN IMPAIRMENT. - ANS 30
WHAT DOES "OOS" STAND FOR? - ANS OUT OF SERVICE
D
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - ANS
TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY
SECTIONAL VALVES. - ANS MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - ANS DRAIN TEST RESULTS
, GREEN TAGS INDICATE THAT __________. - ANS NO IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - ANS MAIN CONTROL
VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. - ANS RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE
THE SYSTEM IS FULLY OUT OF SERVICE. - ANS WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE
R
THE SYSTEM IS PARTIALLY OUT OF SERVICE. - ANS BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL
STATION AND OCCUPANTS. - ANS INSURANCE
U
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - ANS IMPAIRMENT
LA
COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER
THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - ANS
50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
C
____________. - ANS MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE
DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - ANS RECORDS
O
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT
PROCEEDINGS. - ANS REVOCATION
D
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: - ANS REFRIGERATION OPERATING ENGINEER, HIGH
PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND
SPRINKLER SYSTEMS. - ANS MASTER FIRE SUPPRESSION PIPING CONTRACTOR
(MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
_________ SPRINKLER HEADS OR LESS. - ANS 30