S-12 CITYWIDE SPRINKLER SYSTEMS
EXAM GUIDE QUESTIONS WITH
CORRECT ANSWERS 2025
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - Correct Ans-OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - Correct Ans-3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - Correct Ans-IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - Correct Ans-
1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - Correct Ans-1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS. - Correct Ans-8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
Correct Ans-OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - Correct Ans-30
WHAT DOES "OOS" STAND FOR? - Correct Ans-OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - Correct
Ans-TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - Correct Ans-MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER. - Correct Ans-DRAIN TEST RESULTS
S-12 CITYWIDE
, S-12 CITYWIDE
GREEN TAGS INDICATE THAT __________. - Correct Ans-NO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - Correct Ans-MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________
TAG PLACED ON THE MAIN CONTROL VALVE. - Correct Ans-RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - Correct Ans-WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - Correct Ans-BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - Correct Ans-INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - Correct Ans-
IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING. - Correct Ans-50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________. - Correct Ans-MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - Correct
Ans-RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - Correct Ans-REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS: - Correct Ans-REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - Correct Ans-MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
S-12 CITYWIDE