S-12 CITYWIDE SPRINKLER SYSTEMS Questions
and Verified Answers 100% Correct
Grade A Spring 2024/2025
1. THE IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - answers>OWNER
2. RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A
MIN. OF__________ YEARS. - answers>3
3. THE BUILDING OWNER SHALL ASSIGN A(N) TO COMPLY WITH
REQUIREMENTS. - answers>IMPAIRMENT COORDINATOR
4. REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - answers>1
5. SHUTDOWNS AFFECTING MORE THAN FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - answers>1
6. NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE
WITHIN HOURS. - answers>8
7. FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY
REPORT CONDITION TO THE AND THE FIRE DEPT. - answers>OWNER OF
THE BUILDING
8. IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN DAYS OR
IT WILL BE CONSIDERED AN IMPAIRMENT. - answers>30
9. WHAT DOES "OOS" STAND FOR? - answers>OUT OF SERVICE
ONLYSTUDENTS 1
,ONLYSTUDENTS 2024/2025 ALL THE BEST
10. OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING AT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - answers>TAGS
11. A SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY
SECTIONAL VALVES. - answers>MASTER FIRE SUPPRESSION PIPING CONTRACTOR
12. SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - answers>DRAIN TEST RESULTS
13. GREEN TAGS INDICATE THAT . - answers>NO IMPAIRMENT WAS FOUND
14. GREEN TAGS WILL BE PLACED ON THE . - answers>MAIN CONTROL VALVE
15. SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A TAG
PLACED ON THE MAIN CONTROL VALVE. - answers>RED
16. A DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEMIS FULLY OUT OF SERVICE. - answers>WHITE
17. A DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS PARTIALLY OUT OF SERVICE. - answers>BLUE
18. THE IMPAIRMENT COORDINATOR WILL NOTIFY THE CARRIER, CENTRAL
STATION AND OCCUPANTS. - answers>INSURANCE
19. PRIOR TO RETURNING A SYS. TO SERVICE, THE SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - answers>IMPAIRMENT
COORDINATOR
20. GLYCERIN NOT GREATER THAN PERCENT OR GLYCOL NOT GREATHER THAN
PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - answers>50, 40
ONLYSTUDENTS 2
, ONLYSTUDENTS 2024/2025 ALL THE BEST
21. THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
. - answers>MAIN CONTROL VALVE
22. SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - answers>RECORDS
23. FAILURE TO MAKE INSPECTIONS MAY RESULT IN OF THE COF AND COURT
PROCEEDINGS. - answers>REVOCATION
24. THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE
FOLLOWING CERTS: - answers>REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
25. A CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND
SPRINKLER SYSTEMS. - answers>MASTER FIRE SUPPRESSION PIPING CONTRACTOR
(MFSPC)
26. A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
SPRINKLER HEADS OR LESS. - answers>30
27. ABOUT PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - answers>96
28. WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF TO PREVENT THE
SYSTEM FROM FREEZING. - answers>40 FAHRENHEIT
29. VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - answers>COLD
WEATHER
30. SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE HEATED TO
PREVENT FREEZING. - answers>DRY PIPE
ONLYSTUDENTS 3