What must owners and operators do if their UST fails the internal lining inspection
and cannot be repaired according to a code of practice? - answer-Permanently close
the UST
T/F Cathodic protection tester can design field-installed cathodic protection systems
- answer-False
T/F Owners and operators have 30 days to respond to an active alarm on their
automatic tank gauging console. - answer-False
T/F An inconclusive result for SIR means an owner and operator has not performed
release detection for that month. - answer-True
How many years must owners and operators maintain performance claims for their
release detection method? - answer-5 Years
Owners and operators with 100 or fewer USTs must have ____ dollars aggregate
coverage for tanking corrective action and compensating third parties - answer-1
Million
T/F Owners and operators may use a combination of financial mechanisms to
comply with the financial responsibility requirements. - answer-True
T/F Tanks less than 10,000 gallons installed after April 11, 2016 do not have to
meet the secondary containment requirement. - answer-False
Owners and operators must notify EPA at least 30 days prior to permanently closing
an UST system or performing a change-in-service by doing what? - answer-Call EPA
E-mail EPA
Mail by U.S Postal Service
Containment sumps include which of the following? - answer-Under-Dispenser
Containment
Submersible Turbine pump sump
Transition Sump
Owners and operators must demonstrate compatibility for which of the following
stored substances? - answer-B50
E15
T/F All components of UST systems are designed for all blends of ethanol in the fuel.
- answer-False
T/F Double-walled spill buckets where the space between the walls of the spill
bucket is no longer monitored at least 30 days must be tested for liquid tightness
within 1 year after monitoring ceases. - answer-False
, What percent of piping can an owner or operator repair and not have to replace the
piping with secondarily contained piping? - answer-Less than 50 percent
T/F Owners and operators need to check hand held release detection equipment for
operability and serviceability at least annually - answer-True
How often must owners and operators conduct containment sump testing for
containment sumps used for piping interstitial monitoring? - answer-3 years
T/F Manual tank gauging can be used to meet the release detection monitoring
requirement for any size tank. - answer-False
T/F Pressurized piping must use an automatic line leak detector. - answer-True
Automatic line leak detectors must be capable of detecting a release of ____ galls
per hour at a pressure of _____ PSI within 1 hour - answer-3 Gallons per hour at 10
PSI
How often must an UST be monitored for releases using release detection? -
answer-30 days
Select the equipment used in UST systems installed after October 13, 2015 where
the first three-year test or inspection must take place at installation. - answer-
Automatic shutoff devices, high level alarms, and single-wall spell buckets receiving
deliveries of more than 25 gallons installed after October 13th, 2015 must have a
first three-year test or inspection at installation.
Select the spill and overfill prevention equipment installed before October 13, 2015,
where the first three-year test or inspection must take place by October 13, 2018. -
answer-All of the equipment shown requires the first three-year test or inspection
T/F Owners and operators are not required to perform release detection during
temporary closure if the UST is empty. - answer-True
How long must records of operators training be maintaned? - answer-As long as the
operator is designated at the facility.
T/F Operator training records must be in paper format and may not be maintained
electronically. - answer-False
T/F The two main types of corrosion protection on upgraded steel tanks are cathodic
protection and internal lining. - answer-True
As stated in the federal UST regulation, a spill or overflow of how many gallons that
results in a release of petroleum to the environment mist be reported to the
implementing agency? - answer-Greater than 25 Gallons
T/F For tanks installed after April 11, 2016 continuous in tank monitoring is an
allowable form of release detection. - answer-False