solutions -personalized success
Appears to be
1. 1. The purpose of inspection shall be to verify that the
condition and is
pump assembly
free from physical
damage
1 Pump house
2. 2.The 5 pertinent visual observations specified in the
NFPA 25 checklist that shall be performed weekly are condition 2 pump
system conditions
3 electrical sys-
tem conditions
Diesel engine sys-
tem conditions
5 steam system
conditions
3. 3.Part of the check of the pump house conditions is served to be
that :
4. 4. During the weekly inspection the pump suction
discharge and bypass valves should be observed to
be :
5. 05. During the weekly inspection , the suction reser-
voir should be observed to be :
6. 6. As observed during the weekly inspections wet pit
suction screens should be
7. 7. During the weekly inspection of the pump assem-
bly the controller pilot light should be
8. 8. During the weekly inspection of the pump assem-
bly the transfer switch normal pilot light should be
9. 9 During the weekly inspection of the pump assembly
the isolating switch should be observed to be
10. 10 During the weekly inspection of the pump assem-
bly the reverse phase alarm pilot light should be ob-
, Cal. Fire Weekly Firepump Cert. Sample Test-with 100% verified
solutions -personalized success
ventilating louversare free to operate
OB fully open
A full
Unobstructed andin place
Illuminated (poweron)
Illuminated (poweron)
Closed Off
, Cal. Fire Weekly Firepump Cert. Sample Test-with 100% verified
solutions -personalized success
11. 11. During the weekly inspection of the pump assem- On
bly the normal phase rotation pilot light should be
observed to be
12. 12, during the weekly inspection of the pump as- Normal
sembly the oil level in the vertical motor sight glass
should be observed to be
13. 13.During the weekly inspection of the pump assem- Two-thirds full
bly the fuel tank should be observed to be
14. 14.during the weekly inspection of the pump as- Auto
sembly the controller selector switch should be in
position
15. 15. During the weekly inspection of the pump assem- Off
bly all alarm pilot lights should be
16. 16.During the weekly inspection of the pump assem- Time
bly the engine running meter is reading
17. 17. During the weekly inspection of the pump assem- Right angle
bly the oil level in the gear drive should be
normal
18. 18. During the weekly inspection of the pump assem- Normal
bly the electrolyte level in batteries should read
19. 19. A weekly test of the fire pump assemblies shall be Without flowing
conducted water
20. 20. The pump test shall be conducted by starting the True
pump automatically
21. 21. A weekly test of the fire pump assembly shall 10 minutes
be conducted by starting the pump without flowing
water. The electric pump shall be run a minimum of.
22. 30 minutes