Maine Fuel Board Tank Setter Practice
Questions and Answers
What is the minimum distance between a direct fire vaporizer and
container shut off valves? - Answer✔️✔️-5ft
What is the minimum distance between direct fire vaporizer and an above
ground LP container? - Answer✔️✔️-10ft
What type of fencing is allowed around an LP tank? - Answer✔️✔️-6ft high
industrial fencing
What statement between static electricity and relative humidity is true? -
Answer✔️✔️-When humidity is low static charge is high
When is a permit required for a rooftop installation of an LP tank? -
Answer✔️✔️-Prior to the installation
When is it Okay to use a single stage regulator? - Answer✔️✔️-1.) Only in
small portable appliances and out door cooking appliances 100,000 btu
or less.
What is the specific gravity of LP gas at 60 degrees F? - Answer✔️✔️-1.5
What is the flame temp of LP gas? - Answer✔️✔️-3593 degrees F
How far must the relief valve be piped above an underground 2000 gallon
wc tank? - Answer✔️✔️-7ft
1
, ©SOPHIABENNET@2024-2025 Thursday, August 22, 2024 10:21 AM
How often does a technician need to undergo refresher training? -
Answer✔️✔️-Every 3 years
What is the Max working pressure of CSST piping? - Answer✔️✔️-5psi
What is the Max working pressure of Polyethylene (PE) piping? -
Answer✔️✔️-30psi
What is the voltage for a successful cathodic test? - Answer✔️✔️--.85 volts
(Negative .85 volts)
After the first successful cathodic test how soon after must the second test
be performed? - Answer✔️✔️-12-18 months
How far must an LP tank over 125 gallons be located from other flammable
liquid tanks such as an oil tank? - Answer✔️✔️-20ft
Tanks that are between 125-500 WC must be how far from property line? -
Answer✔️✔️-10ft
Tanks that are between 501-2,000 WC must be how far from property line?
- Answer✔️✔️-25ft
Underground tanks that are 2,000 WC or less must be how far from
property line? - Answer✔️✔️-10ft
Emergency shut offs must be how far from point of liquid transfer? -
Answer✔️✔️-Min 25ft Max 100ft