Questions With Correct Answers
Cooling Correct Answer-Heat Exchangers Shall Be Checked For _____
Water Flow.
Off Correct Answer-All Alarm Pilot Lights Should Be In What State?
Ventilating Louvers Are Free To Operate & Heat Is Adequate, Not Less
Than 40 Degrees F For Diesel Pump Rooms Correct Answer-There Are
2 Requirements Listed Under Pump House Conditions, What Are They?
True Correct Answer-Weekly Inspection Requires Verification That The
Pump Suction Discharge And Bypass Valves Should Be Fully Open. T
Or F 4
Green Correct Answer-When Verifying The Electrical System
Conditions,The Controller Pilot Light Should Be _____.
Weekly (Visual Inspection) Correct Answer-Diesel Engine Fuel Tank
Level, Float Switch And Solenoid Valve Operation Shall Be Checked
_____.
Diesel Correct Answer-What Kind Of Pump Do You Record The Time
To Crank?
, Pump House Conditions, Pump System Conditions, Electrical System
Conditions, Diesel Engine System Conditions, And Steam Engine
Conditions. Correct Answer-The Pertinent Visual Obsevation Categories
Required To Be Inspected Weekly Check Lists Are _____.
Appears To Be In Operating Condition And Is Free From Physical
Damage. Correct Answer-What Is The Purpose Of Inspecting The Pump
Assembly?
Illuminated. Correct Answer-The Transfer Switch Normal Pilot Light
Should Be _____.
Closed. Correct Answer-The Isolating Switch For Electric Pumps
Should Be _____.
Overheating. Correct Answer-Pump Packing Boxes, Bearings And
Casings Shall Be Checked For...
Off. Correct Answer-The Reverse Phase Alarm Pilot Light For Electric
Pumps Should Be _____.
Deficiencies Not Evident By Inspection. Correct Answer-The Purpose
Of Testing The Pump Assembly Is To Ensure Automatic Manual
Operation Upon Demand And Continuous Delivery Of The Required
System Output. An Additional Purpose Is To Detect...
On. Correct Answer-The Normal Phase Rotation Pilot Should Be _____.