What are the requirements for a new patient room door for a healthcare occupancy? - Answer45.5 inches wide & smoke tight What are the typical contractor responsibilities during healthcare construction? - AnswerOperations manuals Maintenance Manuals Punch list TAB Reports Medical gas verification What is a TAB report? - Answer-Testing Adjustment Balancing Report What are typically NOT a contractor's responsibility during healthcare construction? - AnswerFinal cleaning Training What type of rooms require 2 total outdoor air changes? - Answer-Patient room NICU ICU CCU Airborne Infection Isolation Room Protective environment room Radiology waiting ED waiting Triage What type of rooms require 3 total outdoor air changes? - Answer-Procedure room What type of rooms require 4 total outdoor air changes? - Answer-OR room Delivery room What type of rooms require 4 total air changes? - Answer-Patient room What type of rooms require 6 total air changes? - Answer-NICU ICU CCU What type of rooms require 12 total air changes? - Answer-Isolation room Protective environment room ED Waiting Radiology waiting Triage