CHC and CHFM Exam Study Guide | Verified | Latest Update 2024
Fire protection for a new construction sleeping suite not exceeding 7500 sqft - The room must have a sprinkler system and complete smoke detection OR sprinkler system with QRS or residential sprinklers Fire protection for a new construction sleeping suite greater than 7500 sqft - The room mush have direct supervision AND total coverage automatic smoke detection and sprinkler system protection with QRS or residential sprinkler Fire protection for existing construction not exceeding 5000 sqft. - The room must have automatic smoke detection Fire protection for existing construction up to 10,000 sqft - Additional fire protection - Sprinkler protection and smoke partitions. Fire protection for a non sleeping suite up to 12,500 sqft - The facility must have either quick response sprinklers or completed smoke detection Fire protection for a non sleeping suite up to 15,000 sqft. - The facility must have BOTH quick response sprinklers and complete smoke detection Where can you store up to 300 cubic feet of medical gas (12 E Cylinders) - They can be stored in a smoke zone without seperation. Fire protection for a medical gas storage room with 300 cubic feet to 3000 cubic feet worth of Medical Gas - It is permitted in a non rated room with sprinkler protection and clearance from combustibles