CHC and CHFM Exam questions with correct answers
Fire protection for a new construction sleeping suite not exceeding 7500 sqft Correct Answer-The room must have a sprinkler system and complete smoke detection OR sprinkler system with QRS or residential sprinklers Fire protection for a new construction sleeping suite greater than 7500 sqft Correct Answer-The room mush have direct supervision AND total coverage automatic smoke detection and sprinkler system protection with QRS or residential sprinkler Fire protection for existing construction not exceeding 5000 sqft. Correct Answer-The room must have automatic smoke detection Fire protection for existing construction up to 10,000 sqft Correct Answer-Additional fire protection - Sprinkler protection and smoke partitions. Fire protection for a non sleeping suite up to 12,500 sqft Correct Answer-The facility must have either quick response sprinklers or completed smoke detection Fire protection for a non sleeping suite up to 15,000 sqft. Correct Answer-The facility must have BOTH quick response sprinklers and complete smoke detection Where can you store up to 300 cubic feet of medical gas (12 E Cylinders) Correct Answer-They can be stored in a smoke zone without seperation. Fire protection for a medical gas storage room with 300 cubic feet to 3000 cubic feet worth of Medical Gas Correct Answer-It is permitted in a non rated room with sprinkler protection and clearance from combustibles