It is recommended gauge calibration statements be kept on file for ____ years -
ANSWER-7 years
The temperature range for a Backflow preventer test kit is ____ degrees -
ANSWER-33/180 degrees
The maximum working pressure of a Backflow preventer test kit is ____ psi -
ANSWER-200
The graduations on a line pressure gauge will resolve pressure to ____ psi -
ANSWER-5
The following markings are required on the test kit except - ANSWER-Critical
level
A differential gauge is used to test the following except - ANSWER-AVB's
The five gauge valves are - ANSWER-Soft seated needle valves
A field test kit is not tested for line pressures in excess of ____ psi - ANSWER-
300
,The American Society of Sanitary Engineering 1013 Product Standards set the
max allowable pressure loss through a 4 in RPZ assembly during glow at -
ANSWER-14 psi
The American Society of Sanitary Engineering 1015 Product Standard sets the
maximum allowable pressure loss through a 4 inch double check valve
assembly during rated flow at - ANSWER-10 psi
To operate, a barometric loop must be installed - ANSWER-Thirty five feet
above the highest outlet
Residual pressure is determined in a system during a ____ condition -
ANSWER-Flow
At sea level, atmospheric pressure is defined as ____ psi - ANSWER-14.7 psi
Pressure can be expressed in "feet of head" as well as the more common
"pounds per square inch" (psi). To convert feet of head to psi you must -
ANSWER-Multiply by .433
A check valve direction of flow differential pressure test will have a high
pressure hose attached at the inlet test cock and - ANSWER-Low pressure hose
attached to outlet test cock
With normal flow, spill resistant vacuum breakers ____ must close before the
____ opens - ANSWER-Air inlet valve/ check valve
Field test equipment should be checked for calibration - ANSWER-Annually
, The best method of measuring pressure differential in the range of two to five is
a - ANSWER-Differential pressure gauge
Wen choosing the type of Backflow prevention device, method, or assembly
required to protect the water supply, the most important factor to consider is -
ANSWER-Degree of hazard
When a direct connection is required between the domestic water service and
the sanitary sewer the proper protection required is - ANSWER-No direct
connection is allowed
A dual check with an intermediate vent is used primarily for - ANSWER-Low
pressure residential boilers
A hose connection vacuum breaker maintenance includes - ANSWER-Draining
for winterization
When both shut off valves are closed on a RP and test cock 2 is opened, a tester
should expect - ANSWER-Relief valve discharge
A common application for a dual check valve is at - ANSWER-Residential
service connection
Tightly closing shut off valves are important to provide - ANSWER-Accurate
field test results
The dual check valve standard does not require - ANSWER-Test cocks
A dual check valve installed at the meter / service connection provides
Backflow protection from - ANSWER-Backpressure & backsiphonage