Complete 40 Verified Q&A with Answers &
Rationales for Exam Prep
Q1
For a 200A residential service, what minimum size copper THWN conductor is required for the
ungrounded service conductors?
A. 2/0 AWG
B. 1/0 AWG
C. 3/0 AWG
D. 4/0 AWG
Answer: A
Rationale: Per NEC Table 310.12(A) for 200A residential services, 2/0 AWG copper is the minimum. 1/0
AWG is for 150A, 3/0 AWG for 250A, and 4/0 AWG for 300A services.
Q2
When installing a 20A branch circuit in a commercial garage, which wiring method is prohibited by Oregon
amendments?
A. EMT
B. Type MC cable
C. Type NM cable
D. Rigid metal conduit
Answer: C
Rationale: Oregon amendments prohibit Type NM cable in commercial garages due to physical protection
and fire safety concerns. EMT, MC, and RMC are permitted with proper support and protection.
, Q3
What is the minimum burial depth for PVC conduit containing 480V feeders under a residential driveway?
A. 18 inches
B. 24 inches
C. 12 inches
D. 30 inches
Answer: B
Rationale: NEC Table 300.5 requires 24 inches of cover for PVC conduit under a residential driveway for
circuits over 300V. 18 inches is for residential branch circuits, 12 inches for GFCI-protected residential,
and 30 inches is not standard.
Q4
In a 120/240V single-phase panel, what is the maximum allowable neutral-to-ground bond locations?
A. Only at the service disconnect
B. At each subpanel
C. At the meter base only
D. At the first outlet
Answer: A
Rationale: NEC 250.24(A)(5) prohibits neutral-to-ground bonds at subpanels; the bond must be at the
service disconnect. Meter base bonding is not permitted, and first outlet bonding is unsafe.
Q5
What is the maximum overcurrent protection for a 10 HP, 460V, 3-phase motor with a marked service
factor of 1.15?
A. 30A
B. 25A
C. 20A
D. 35A
Answer: A
Rationale: NEC Table 430.250 gives 14A FLC for 10 HP at 460V; 430.52 allows 250% for inverse-time
breakers, yielding 35A, but standard size per 240.6 is 30A. 25A and 20A are undersized; 35A is not a
standard size.