Prepare for the NETA III Certified Electrical Testing Technician exam with this set of practice questions and detailed rationales based on ANSI/NETA ETT-2026. Topics include circuit breaker timing, insulation resistance and polarization index, transformer turns ratio, ground grid resistance, relay coordination, power quality, cable testing, DGA, and motor overload settings. Each answer explains the correct choice and references the relevant standard, helping you understand the code and apply it on the job.

Content preview

, Question 1
A 15 kV vacuum circuit breaker undergoes timing tests. The closing time is 85
ms, opening time 45 ms, and pole discrepancy 3 ms. Per ANSI/NETA
ETT-2026, which parameter exceeds the maximum allowable limit for this
breaker type?
A. Closing time only
B. Opening time only
C. Pole discrepancy only
D. Both closing time and pole discrepancy
Correct Answer: A - Closing time only


RATIONALE
NETA ETT-2026 Table 100.7 specifies maximum closing time of 80
ms for vacuum breakers; 85 ms exceeds this. Opening time (45 ms)
and pole discrepancy (3 ms) are within limits (50 ms and 5 ms,
respectively). Thus, only closing time is non-compliant.

Question 2
During insulation resistance testing of a 5 kV motor winding, readings at 1
minute and 10 minutes are 500 M and 800 M, respectively. The winding
temperature is 40°C. What is the polarization index (PI) and its interpretation
per NETA ETT-2026?
A. PI = 1.6, acceptable
B. PI = 1.6, questionable; investigate
C. PI = 0.625, unacceptable
D. PI = 2.0, excellent
Correct Answer: B - PI = 1.6, questionable; investigate




Page 2

, RATIONALE
PI = 10-min IR / 1-min IR = 800/500 = 1.6. NETA ETT-2026
considers PI 2.0 as good, 1.5-2.0 as questionable requiring further
investigation, and <1.5 as poor. A PI of 1.6 indicates marginal
insulation condition, necessitating additional tests like step-voltage or
dissipation factor.

Question 3
A transformer turns ratio test on a 13.8 kV-480 V, 1 MVA, delta-wye
transformer yields a measured ratio of 28.5:1. The nameplate ratio is 28.75:1.
What is the percent error, and does it comply with NETA ETT-2026?
A. 0.87% error, complies
B. 0.87% error, does not comply
C. 1.0% error, complies
D. 1.0% error, does not comply
Correct Answer: A - 0.87% error, complies


RATIONALE
Percent error = |28.5 - 28.75| / 28.75 × 100 0.87%. NETA ETT-2026
allows a maximum ratio error of ±0.5% for transformers. Since 0.87%
exceeds this, it does not comply, but the question asks for error and
compliance; 0.87% is correct, but compliance is 'does not
comply'-however, option A says complies, which is wrong. Wait: The
correct answer should be B. Let me recalc: 28.75-28.5=0.25;
0.25/28.75=0.008695=0.87%. NETA Table 100.3 allows ±0.5% for
turns ratio. So 0.87% > 0.5%, so does not comply. Thus correct is B. I
need to correct my answer. The initial correct was A, but it's B. Let me
fix: The correct option is B. Explanation: Error is 0.87%, which
exceeds the ±0.5% tolerance, so it does not comply.




Page 3

, Question 4
A ground grid resistance test using the fall-of-potential method yields 3.5 . The
system is a 13.8 kV substation with a fault current of 10 kA and a clearing time
of 0.5 s. Per IEEE 80 and NETA ETT-2026, what is the maximum allowable
grid resistance to ensure step and touch voltages are safe?
A. 1.0
B. 2.5
C. 5.0
D. 10.0
Correct Answer: C - 5.0


RATIONALE
IEEE 80 does not specify a fixed maximum grid resistance; instead, it
requires that step and touch voltages be within tolerable limits.
However, NETA ETT-2026 Table 100.18 suggests a target of 5 for
substation grounds, but the actual criterion is safety. A 3.5 reading is
generally acceptable if step/touch voltages are safe. Among options,
5.0 is the typical maximum guideline.

Question 5
A protective relay coordination study shows that the upstream feeder breaker's
time-delay setting is 0.3 s, while the downstream breaker's instantaneous
setting is 0.1 s. What is the coordination time interval (CTI), and does it meet
NETA ETT-2026 recommendations?
A. 0.2 s, meets
B. 0.2 s, does not meet
C. 0.4 s, meets
D. 0.4 s, does not meet
Correct Answer: A - 0.2 s, meets




Page 4

Document information

Uploaded on
September 30, 2026
Number of pages
94
Written in
2026/2027
Type
Exam (elaborations)
Contains
Questions & answers
$30.00

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
CaseHero
3.8
(4)
Sold
21
Followers
0
Items
6413
Last sold
13 hours ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions