receptacles outlets installed for a appliance in a dwelling unit, such as a laundry
equipment shall be located within of the intended location of the appliance -
ANSWER-6ft
there shall be a minimum of one branch circuit for laundry outlet - ANSWER-20
amp
manhole openings for personnel shall be located where they are not directly above
electrical equipment or conductors in the enclosure. where this is not practicable -
ANSWER-a protective barrier or a fixed ladder shall be provided
,two or more small appliance branch circuits shall be provided to supply power for
receptacle outlets in the dwelling unit kitchen, dining room, breakfast room, or
similar dining areas - ANSWER-20 amp
the work space in front of electrical equipment shall not be less than wide . or the
width of the equipment which ever is greater - ANSWER-30"
in locations where electrical equipment is likely to be exposed to enclosures or
guards shall be so arranged and of such strength as to prevent such damage -
ANSWER-physical damage
What is the feeder or service calculated load for a waste disposal (940 VA),
dishwasher (1250VA), a trash compactor (1100VA), and a waste heater
(4500VA)? - ANSWER-5843 VA
GFCI protection at a carnival is not required for equipment at a circuit if the
receptacle is of the_______ type - ANSWER-locking
Where cables or nonmetallic raceways are installed through bored holes in joists,
rafters, or wood members, holes shall be board so that the edge of the hole is
________ the nearest edge of the wood member - ANSWER-not less than 1 1/4in
from
To guard live parts over 50V but less than 600V, equipment is permitted to be
______ - ANSWER-located in a room only accessible to qualified persons, located
on a balcony accessible only qualified persons, and elevated 8ft or more above
floor or other working surfaces
, How many receptacles are required within the perimeter of a balcony, deck, porch
with an unusable are of less than 20 SQ feet - ANSWER-1
Overhead feeder conductors shall have a minimum_________ vertical clearance
over residential property and driveways, as well as those commercial areas not
subject to truck traffic, where voltage is limited to 300 volts- to- ground -
ANSWER-12 feet
Where rear access is required to work on de-energized parts on the back of
enclosed equipment, a minimum working space of________ horizontally shall be
provided - ANSWER-36 inches
What is the maximum run length of an 18 AWG fixture wire that is tapped onto s
20 amp branch circuit? - ANSWER-50'
When the service disconnecting means power-operated switch or circuit breaker, it
shall be able to be opened by hand in the event of a _____ - ANSWER-power
supply failure
For equipment rated 1200 Amps or more and over 6ft wide that contains
overcurrent devices, switching devices, or control devices, there shall be one
entrance to and egress from the required working space not less than 24in. wide
and ______ high at each end of the working spaced - ANSWER-6ft 6 in
Conductors are considered outside buildings when they are buried under not less
than__________ - ANSWER-2 inches
In straight pull, the length of the box shall not be less than ________ times the
trade size of the largest raceway - ANSWER-8