●● At sea level the atmospheric pressure is 14.7 psia. What is the
absolute pressure of a 50 psig (gauge pressure) system at sea level?
A 64.7 psia
B 50 psia
C 34.7 psia
D 60 psia
Answer: 64.7 psia
●● Medical Gas _______________________________ shall be able to
describe how to find and implement manufacturer specific maintenance
requirements for the medical gas and vacuum system components per
ASSE 6000 Annex D and CGA E.10.
A Supplier or Distributor
B Maintenance Personnel
C Authority having jurisdiction
D Verifier or Inspector
Answer: Maintenance Personnel
,●● Medical Gas Maintenance Personnel shall be able to identify and
describe the hazards resulting from improper maintenance of medical
gas and vacuum systems, including:
A Flow
B Cross Connections
C Contaminants
D All of the above
Answer: All of the above
●● ASSE 6000 daily checks of bulk liquid systems include all of the
following with the exception of
______________.
A Primary and Reserve (if equipped) Tank Contents
B Pressure Dew Point Temperature
C Leaks or Unusual Icing
D Proper pressure maintained
Answer: Pressure Dew Point Temperature
●● Per ASSE 6000 Annex D typical maintenance procedures include
_______________ checks of the Medical Air Moisture removal system
(after cooler, dryer drain, receiver drain, sight glass, etc.).
A Daily
B Weekly
,C Monthly
D Annually
Answer: Daily
●● Per ASSE 6000 Annex D the Medical Air __________ is typically
checked daily.
A Dew Point Monitor
B Carbon Monoxide Monitor
C Filter Condition
D Both A & B
E All of the above
Answer: Both A & B
●● Typical monthly checks, per ASSE 6000 Annex D, of area alarms
include all of the following except :
A Audible Signal
B Visual Signals
C Emergency Instructions
D Gauge Pressure Read Outs
Answer: Emergency Instructions
●● Per ASSE 6000 Annex D, the medical air compressor intake location
and filter condition should be checked _______________.
, A Daily
B Weekly
C Quarterly
D Annually
Answer: Quarterly
●● Minimum Maintenance Schedule, per ASSE 6000 Annex D, should
include annual checking of ________________ for Flow,
Pressure/Vacuum, Damage, and Wear.
A All outlets & inlets
B All critical care outlets & inlets
C 50% of all critical care outlets
D Annual testing of outlets & inlets is not recommended
Answer: All critical care outlets & inlets
●● Per ASSE 6000 Annex D the medical air compressor
_____________________ should be calibrated annually.
A Dew Point & Carbon Monoxide Monitors
B Carbon Monoxide Monitor Only
C Gauges
D Motor Overloads
Answer: Dew Point & Carbon Monoxide Monitors
QUESTIONS AND CORRECT ANSWERS
●● At sea level the atmospheric pressure is 14.7 psia. What is the
absolute pressure of a 50 psig (gauge pressure) system at sea level?
A 64.7 psia
B 50 psia
C 34.7 psia
D 60 psia
Answer: 64.7 psia
●● Medical Gas _______________________________ shall be able to
describe how to find and implement manufacturer specific maintenance
requirements for the medical gas and vacuum system components per
ASSE 6000 Annex D and CGA E.10.
A Supplier or Distributor
B Maintenance Personnel
C Authority having jurisdiction
D Verifier or Inspector
Answer: Maintenance Personnel
,●● Medical Gas Maintenance Personnel shall be able to identify and
describe the hazards resulting from improper maintenance of medical
gas and vacuum systems, including:
A Flow
B Cross Connections
C Contaminants
D All of the above
Answer: All of the above
●● ASSE 6000 daily checks of bulk liquid systems include all of the
following with the exception of
______________.
A Primary and Reserve (if equipped) Tank Contents
B Pressure Dew Point Temperature
C Leaks or Unusual Icing
D Proper pressure maintained
Answer: Pressure Dew Point Temperature
●● Per ASSE 6000 Annex D typical maintenance procedures include
_______________ checks of the Medical Air Moisture removal system
(after cooler, dryer drain, receiver drain, sight glass, etc.).
A Daily
B Weekly
,C Monthly
D Annually
Answer: Daily
●● Per ASSE 6000 Annex D the Medical Air __________ is typically
checked daily.
A Dew Point Monitor
B Carbon Monoxide Monitor
C Filter Condition
D Both A & B
E All of the above
Answer: Both A & B
●● Typical monthly checks, per ASSE 6000 Annex D, of area alarms
include all of the following except :
A Audible Signal
B Visual Signals
C Emergency Instructions
D Gauge Pressure Read Outs
Answer: Emergency Instructions
●● Per ASSE 6000 Annex D, the medical air compressor intake location
and filter condition should be checked _______________.
, A Daily
B Weekly
C Quarterly
D Annually
Answer: Quarterly
●● Minimum Maintenance Schedule, per ASSE 6000 Annex D, should
include annual checking of ________________ for Flow,
Pressure/Vacuum, Damage, and Wear.
A All outlets & inlets
B All critical care outlets & inlets
C 50% of all critical care outlets
D Annual testing of outlets & inlets is not recommended
Answer: All critical care outlets & inlets
●● Per ASSE 6000 Annex D the medical air compressor
_____________________ should be calibrated annually.
A Dew Point & Carbon Monoxide Monitors
B Carbon Monoxide Monitor Only
C Gauges
D Motor Overloads
Answer: Dew Point & Carbon Monoxide Monitors