Extinguishers Practice Test 1
Study Guide | Certification Exam
Prep
2026/2027
, Examples of extinguishers for protecting class B hazards D. A & B Only
are
A. aqueous film forming foam
B. Carbon dioxide
C. Wet chemical
D. A and B only
E. all the above
A church is classified as what type of hazard? A. light (low) hazard
A. light (low) hazard
B. ordinary (moderate) hazard
C. extra (high) hazard)
D. special (unusual) hazard
A parking garage is classified as what type of hazard? B. ordinary (moderate) hazard
A. light (low) hazard
B. ordinary (moderate) hazard
C. extra (high) hazard)
D. special (unusual) hazard
A boat or aircraft servicing is classified as what type of C. extra (high) hazard
hazard?
A. light (low) hazard
B. ordinary (moderate) hazard
C. extra (high) hazard)
D. special (unusual) hazard
Building protection should be provided by fire D. all of the above
extinguishers suitable for what class of fire extinguishers?
A. Class A
B. Class B
C. Class C
D. all of the above
An ordinary hazard occupancy is also designated as a D. moderate
_________ hazard.
A. normal
B. significant
C. medium
D. moderate
The minimum rate single fire extinguisher for an Extra C. 4-A
Class A hazard occupancy...
A. 2-A
B. 2-A 10 BC
C. 4-A
D. 4-A 10BC
The maximum floor area per unit of a rating for an Ordinary A. 1000 sq ft
Class A Hazard Occupancy is...
A. 1000 sq ft
B. 1500 sq ft
C. 2000 sq ft
D. 2500 sq ft
The maximum travel distance to an 80-B extinguisher for B. 50 ft
an Extra B hazard is...
A. 30 ft
B. 50 ft
C. 75 ft
D. 100 ft