BICSI TECHNICIAN EXAM Verified Exam Questions and Answers
Latest update 2026/2027
Question:
L Rating
Answer:
A firestops ability to provide a smoke stop. (air leakage rate)
Question:
To avoid damaging cable jacket, how often must you securely fasten electrical nonmetallic tubing
(ENT)
Answer:
3 Feet so it does not damage the cable
Question:
What is the minimum dedicated power requirement of a telecommunications enclosure
Answer:
120 V ac/20
Question:
The clearance behind the PBB when mounted, should be no less than
Answer:
2inch clearance behind the PBB when mounted
Question:
When installing a plywood backboard, you should use galvanized screws that are a minimum of
______ longer than the depth of the wall covering, including the plywood
Answer:
0.5in
Question:
The use of under carpet telecommunications cable should be limited to
Answer:
The interconnection point between horizontal cabling and UTC is a transition point (TP)
, Question:
Two 90-degree bends are allowed in any one conduit segment. A third bend may be acceptable under
certain situations
Answer:
Runs under 33 feet
Question:
When installing racks and cabinets on an access floor, what should they be secured to?
Answer:
The frame
Question:
When placing cabinets on an access floor, how should the cabinets be aligned?
Answer:
One edge flush with the floor tile cut line
Question:
What is a telecommunications enclosure TE used for?
Answer:
May be used to provide a suitable option for moves, adds, and changes without compromising
infection control measures and other restrictions
Question:
What size threaded rod would you typically use in a heavy duty ladder rack installation?
Answer:
5/8in
Question:
A supplemental bonding network within an ER or data center consisting of a set of conductors formed
into a grid is often associated with what?
Answer:
Access flooring
Question:
Which type of anchor requires a hole to be drilled into the floor where the attachment is to be made?
Answer:
Expansion anchors
Latest update 2026/2027
Question:
L Rating
Answer:
A firestops ability to provide a smoke stop. (air leakage rate)
Question:
To avoid damaging cable jacket, how often must you securely fasten electrical nonmetallic tubing
(ENT)
Answer:
3 Feet so it does not damage the cable
Question:
What is the minimum dedicated power requirement of a telecommunications enclosure
Answer:
120 V ac/20
Question:
The clearance behind the PBB when mounted, should be no less than
Answer:
2inch clearance behind the PBB when mounted
Question:
When installing a plywood backboard, you should use galvanized screws that are a minimum of
______ longer than the depth of the wall covering, including the plywood
Answer:
0.5in
Question:
The use of under carpet telecommunications cable should be limited to
Answer:
The interconnection point between horizontal cabling and UTC is a transition point (TP)
, Question:
Two 90-degree bends are allowed in any one conduit segment. A third bend may be acceptable under
certain situations
Answer:
Runs under 33 feet
Question:
When installing racks and cabinets on an access floor, what should they be secured to?
Answer:
The frame
Question:
When placing cabinets on an access floor, how should the cabinets be aligned?
Answer:
One edge flush with the floor tile cut line
Question:
What is a telecommunications enclosure TE used for?
Answer:
May be used to provide a suitable option for moves, adds, and changes without compromising
infection control measures and other restrictions
Question:
What size threaded rod would you typically use in a heavy duty ladder rack installation?
Answer:
5/8in
Question:
A supplemental bonding network within an ER or data center consisting of a set of conductors formed
into a grid is often associated with what?
Answer:
Access flooring
Question:
Which type of anchor requires a hole to be drilled into the floor where the attachment is to be made?
Answer:
Expansion anchors