Automatic Standpipe System A standpipe system that is attached to a water supply capable of
supplying the system demand at all times and that requires no action
other than opening a hose valve to provide water at hose connections.
Churning A condition in a centrifugal in which the impeller is rotating, but no
water is being discharged.
Combination Standpipe and Sprinkler System A system where the water piping service both 2 1/2in (65) outlet for fire
Department use and oulet for automatic sprinkler
Concealed Sprinkler A recessed sprinkler with a cover plate
Deluge Valve water supply control valve intended to be operated by actuation of an
automatic detection system that is installed in the same area as the
discharge devices. Suitable for HAZARDOUS OCCUPANCIES.
INTENDED USE IS MANUAL AND AUTO
Deludge Sprinkler System A sprinkler system employing open sprinklers that are attached to a
piping system that is connected to a water supply through a VALVE
that is opened of a DETECTION SYSTEM installed in the same area
as the sprinklers
Dry Pipe Sprinkler System A sprinkler system employing automatic sprinklers that are attached to a
piping system containing air or nitrogen under pressure. The release of
the air or nitrogen,(as from the opening of a sprinkler) results in the
water pressure opening a valve known as a dry pipe valve, resulting
in the flow of water into the piping system and out of the fused
sprinklers heads.
Dry Sprinkler A sprinkler secured in an extension nipple that has a seal at the inlet to
prevent water from entering the nipple until the sprinkler operates.
May be configured with an upright, pendent or sidewall sprinkler.
AUTO/NON_AUTO
Dry Standpipe A standpipe system designed to have piping contain water only when
the system is being utilized (NO AUTOMATIC WATER SUPPLY)
, Fire Department Connection A connection, normally on the exterior of the building. (FORMERLY
KNOW AS SIAMESE CONNECTION)
Fire Hose A flexible conduit constructed of one or more reinforcements
(JACKETS),
Fire Hydrant A valve connection on a water supply system having one or more
outlets and that is used to supply hose and fire department pumps with
water.
Bulb Sprinkler A sprinkler operated by heat breaking a glass bulb filled with a non-
freezing liquid with diamiter that vary from 3mm for quick response
sprinklers to 5mm for standard response sprinklers.
Hose Connection a combination of equipment provided for connection of a hose to the
standpipe system that includes a hose valve with a threaded outlet.
Hose Station a combination of a hose rack, hose nozzle, hose, and hose connection.
Impairment Coordinator Person responsible for ensuring the proper safety precautions are
taken when the fire protection system is placed out of service
(designated by the owner)
In Service The Status of hose stored in a hose house, on a rack or reel, or on a fire
apparatus that is available and ready for immediate use at an incident.
Personal Supervision Supervision by the holder of a department certificate who is required to
be personally present on the premises, or other proximate location
acceptable to the department, while the duties for which the certificate
is required is being performed.
Pressure Restricting Device A valve or device designed for the purpose of reducing of reducing the
downstream water pressure under both flowing (residual) and non-
flowing (static) conditions
Pressure Reducing Valve A valve or device designed for the purpose of reducing of reducing the
downstream water pressure under flowing (residual) conditions only.
Pressure Tank A tank using air pressure to supplying water for water-based fire
protection systems. Tank contents to be maintained at one third air to
two thirds water.
Quick Response Sprinkler Head A sprinkler having a fusible link with a response time index (RTI) of 50 or
less.
Recessed Sprinkler A sprinkler in which all or part of the body, other than the shank
thread, is mounted above the ceiling.
Standpipe System An arrangement of piping, valves, and hose connections installed in a
structure to deliver water for fire hoses.
Combination Standpipe and Sprinkler System A system where the fire protection piping services both 21⁄2 in. (65 mm)
outlets for fire department use and outlets for automatic sprinklers.
Static Pressure The measurement of sytem pressure inder NON FLOW CONDITIONS.