As per CAN/ULC S801, on an electrical distribution overhead utility line circuit, verification of voltage
absence can be achieved by: - (ANSWER)Using an approved voltage detector.
Isolation and tagging (no locks) is acceptable on an overhead distribution circuit under some of the
following conditions, EXCEPT for: - (ANSWER)The isolation can be operated from the ground directly at
the base of a structure.
Isolation and tagging (no locks) is acceptable for an overhead distribution circuit under some of the
following conditions: - (ANSWER)1. The isolation point is a physical and visual like a line cut or riser
removed.
2. The isolation point can only be operated by the operating authority or qualified worker.
3. The isolation point is protected from unauthorized access such as vertical height spacing.
Consider that a circuit has been isolated, tagged and grounded. workers returning the next day must: -
(ANSWER)Visually check grounds to verify they are in good order, secure and test for voltage.
For lockout purposes, energy isolating devices shall be labelled or marked using a standardized
nomenclature and format to indicate their function. Identification shall include: - (ANSWER)The
equipment type, energy type, and magnitude.
Utilities often use a permitting system due to special circumstances of which conventional lockout is
impracticable. The following is NOT a justified approach to this process: - (ANSWER)The isolation points
are only simple single step actions.
A high voltage utility or electrical company is authorized to use Complex Lockout (tag permitting) under
what regulatory condition: - (ANSWER)A variance application has been approved by the provincial
authority.
Utilities often use a permitting system due to special circumstances of which conventional lockout is
impracticable. The following are justified approaches to this process: - (ANSWER)1. The isolation points
are located in remote areas with difficult or restricted access.
,CUSP - T&D NEW UPDATE WITH COMPLETE SOLUTIONS 100%
VERIFIED!!! ALREADY GRADED A+ LATEST UPDATE!!
2. The length of time to perform the lockout is impracticable.
3. Excessive numbers of persons required to lockout.
Work on a distribution line must consider the following items when performing isolation and de-
energizing of the circuit.: - (ANSWER)1. Whether there are multiple sources of energy (loop feed) on the
circuit.
2. Is the line isolating device capable of interrupting load.
3. Is the line to be subject to inductive or capacitive charge.
According to the CAN/ULC S801, what is the LEAST DESIRABLE type of fall protection: - (ANSWER)Fall
Arrest System (FAS)
Within Z259.14 standards fall restriction equipment (FRE) may only be leather in subcomponents or
elements that are NOT exposed to: - (ANSWER)A dynamic load.
As per Z259 standards, energy absorbing lanyards shall be classified according to their ability to absorb
the kinetic energy from a fall as follows: - (ANSWER)Class E4 (4.0 kN) and Class E6 (6.0 kN) energy
absorbing lanyards.
Assuming that the fall protection system is correctly being used, in what scenario might the worker still
contact the ground if they fell: - (ANSWER)Working 16 feet up in a bucket truck on distribution secondary
services using a six foot shock absorbing lanyard, connected to the approved bucket anchor.
What is NOT defined as a requirement of temporary vertical life lines as per Z259 standards: -
(ANSWER)100% polypropylene fibers provide the greatest breaking strength.
Requirements of temporary vertical life lines, as per Z259 standards: - (ANSWER)1. Shall be made from
synthetic fibers with breaking strength of 27 kN or greater.
2. They shall be free of splices and knots, except at the terminations.
3. They shall be installed to protect against abrasion and sharp edges.
, CUSP - T&D NEW UPDATE WITH COMPLETE SOLUTIONS 100%
VERIFIED!!! ALREADY GRADED A+ LATEST UPDATE!!
Working on an energized lattice tower requires emergency response consistent with the associated
hazards. What is NOT required as part of the emergency planning: - (ANSWER)Daily practice of tower
rescue method.
Working on an energized lattice tower requires emergency response consistent with the associated
hazards, including: - (ANSWER)1. A means to contact the operating authority to de-energize the circuit.
2. Rescue equipment readily available to quickly and safely lower the worker.
3. Regular rescue practices on tower rescue at an appropriate frequency.
Z259.14 wooden pole choker devices that are designed and tested to restrict a workers fall distance
under dry, wet, and icy conditions are classified as: - (ANSWER)Type AB device.
The voltage limits and mechanical strength of a live line tool is best specified by: - (ANSWER)The
manufacturers requirements.
Live line tools can be modified to meet the needs of the work. What is NOT an acceptable strategy for
tool modification: - (ANSWER)A utility worker has evaluated the tool modification and approved the
change.
Live line tools can be modified to meet the needs of the work. Acceptable strategies for tool modification
include: - (ANSWER)1. Changes to the tool do not violate other applicable standards.
2. The tool has been inspected and tested by a professional engineer.
3. The tool modification was approved by an engineer using applicable standards.
Insulating hot rope (live line rope) is tested in accordance to ASTM F1701. The purpose of this test is to: -
(ANSWER)Determine the current leakage under dry and wet rope conditions.
Live line rigid cover in compliance with CAN/ULC-61229 includes the following pieces or protective
insulating equipment EXCEPT for: - (ANSWER)Insulating line hose.
VERIFIED!!! ALREADY GRADED A+ LATEST UPDATE!!
As per CAN/ULC S801, on an electrical distribution overhead utility line circuit, verification of voltage
absence can be achieved by: - (ANSWER)Using an approved voltage detector.
Isolation and tagging (no locks) is acceptable on an overhead distribution circuit under some of the
following conditions, EXCEPT for: - (ANSWER)The isolation can be operated from the ground directly at
the base of a structure.
Isolation and tagging (no locks) is acceptable for an overhead distribution circuit under some of the
following conditions: - (ANSWER)1. The isolation point is a physical and visual like a line cut or riser
removed.
2. The isolation point can only be operated by the operating authority or qualified worker.
3. The isolation point is protected from unauthorized access such as vertical height spacing.
Consider that a circuit has been isolated, tagged and grounded. workers returning the next day must: -
(ANSWER)Visually check grounds to verify they are in good order, secure and test for voltage.
For lockout purposes, energy isolating devices shall be labelled or marked using a standardized
nomenclature and format to indicate their function. Identification shall include: - (ANSWER)The
equipment type, energy type, and magnitude.
Utilities often use a permitting system due to special circumstances of which conventional lockout is
impracticable. The following is NOT a justified approach to this process: - (ANSWER)The isolation points
are only simple single step actions.
A high voltage utility or electrical company is authorized to use Complex Lockout (tag permitting) under
what regulatory condition: - (ANSWER)A variance application has been approved by the provincial
authority.
Utilities often use a permitting system due to special circumstances of which conventional lockout is
impracticable. The following are justified approaches to this process: - (ANSWER)1. The isolation points
are located in remote areas with difficult or restricted access.
,CUSP - T&D NEW UPDATE WITH COMPLETE SOLUTIONS 100%
VERIFIED!!! ALREADY GRADED A+ LATEST UPDATE!!
2. The length of time to perform the lockout is impracticable.
3. Excessive numbers of persons required to lockout.
Work on a distribution line must consider the following items when performing isolation and de-
energizing of the circuit.: - (ANSWER)1. Whether there are multiple sources of energy (loop feed) on the
circuit.
2. Is the line isolating device capable of interrupting load.
3. Is the line to be subject to inductive or capacitive charge.
According to the CAN/ULC S801, what is the LEAST DESIRABLE type of fall protection: - (ANSWER)Fall
Arrest System (FAS)
Within Z259.14 standards fall restriction equipment (FRE) may only be leather in subcomponents or
elements that are NOT exposed to: - (ANSWER)A dynamic load.
As per Z259 standards, energy absorbing lanyards shall be classified according to their ability to absorb
the kinetic energy from a fall as follows: - (ANSWER)Class E4 (4.0 kN) and Class E6 (6.0 kN) energy
absorbing lanyards.
Assuming that the fall protection system is correctly being used, in what scenario might the worker still
contact the ground if they fell: - (ANSWER)Working 16 feet up in a bucket truck on distribution secondary
services using a six foot shock absorbing lanyard, connected to the approved bucket anchor.
What is NOT defined as a requirement of temporary vertical life lines as per Z259 standards: -
(ANSWER)100% polypropylene fibers provide the greatest breaking strength.
Requirements of temporary vertical life lines, as per Z259 standards: - (ANSWER)1. Shall be made from
synthetic fibers with breaking strength of 27 kN or greater.
2. They shall be free of splices and knots, except at the terminations.
3. They shall be installed to protect against abrasion and sharp edges.
, CUSP - T&D NEW UPDATE WITH COMPLETE SOLUTIONS 100%
VERIFIED!!! ALREADY GRADED A+ LATEST UPDATE!!
Working on an energized lattice tower requires emergency response consistent with the associated
hazards. What is NOT required as part of the emergency planning: - (ANSWER)Daily practice of tower
rescue method.
Working on an energized lattice tower requires emergency response consistent with the associated
hazards, including: - (ANSWER)1. A means to contact the operating authority to de-energize the circuit.
2. Rescue equipment readily available to quickly and safely lower the worker.
3. Regular rescue practices on tower rescue at an appropriate frequency.
Z259.14 wooden pole choker devices that are designed and tested to restrict a workers fall distance
under dry, wet, and icy conditions are classified as: - (ANSWER)Type AB device.
The voltage limits and mechanical strength of a live line tool is best specified by: - (ANSWER)The
manufacturers requirements.
Live line tools can be modified to meet the needs of the work. What is NOT an acceptable strategy for
tool modification: - (ANSWER)A utility worker has evaluated the tool modification and approved the
change.
Live line tools can be modified to meet the needs of the work. Acceptable strategies for tool modification
include: - (ANSWER)1. Changes to the tool do not violate other applicable standards.
2. The tool has been inspected and tested by a professional engineer.
3. The tool modification was approved by an engineer using applicable standards.
Insulating hot rope (live line rope) is tested in accordance to ASTM F1701. The purpose of this test is to: -
(ANSWER)Determine the current leakage under dry and wet rope conditions.
Live line rigid cover in compliance with CAN/ULC-61229 includes the following pieces or protective
insulating equipment EXCEPT for: - (ANSWER)Insulating line hose.