1. A dwelling unit is supplied by a 120/240-volt, single-phase, 3-wire
service. The calculated load is 142 amperes. The service
disconnecting means is located outside at the point where the
service conductors enter the building. Which NEC principle most
directly governs the minimum service rating?
A. The service rating may be 100 amperes because dwelling units are
permitted a minimum 100-ampere service
B. The service rating must be sufficient to carry the calculated load and
comply with applicable service-rating requirements
C. The service rating must always be exactly 200 amperes for a dwelling
D. The service rating is determined only by the largest branch-circuit
rating
Answer: B. The service rating must be sufficient to carry the
calculated load and comply with applicable service-rating
requirements
Rationale: The service equipment must have a rating adequate for the
calculated load. Dwelling-unit provisions establish minimum service
capabilities, but they do not permit a service rating that is inadequate
for the calculated load. The service calculation must account for the
applicable dwelling-unit demand rules and the resulting service rating.
1
, 2. A service supplies a commercial building with a calculated load of
187 amperes. The designer proposes service equipment rated 200
amperes. Which statement is most accurate?
A. The 200-ampere rating is automatically prohibited because the
calculated load is not exactly 200 amperes
B. The service equipment rating may be acceptable because it exceeds
the calculated load, subject to all applicable NEC requirements
C. The equipment must be rated at least 225 amperes
D. The service equipment must be rated exactly 187 amperes
Answer: B. The service equipment rating may be acceptable because
it exceeds the calculated load, subject to all applicable NEC
requirements
Rationale: A service rating does not have to equal the calculated load
exactly. Standard equipment ratings may exceed the calculated load,
provided the selected equipment complies with the NEC, including
conductor ampacity, overcurrent protection, equipment ratings, and
other applicable requirements.
3. Which location generally represents the preferred point for
installing the service disconnecting means under NEC service
requirements?
A. Anywhere inside the building, regardless of distance from the point
of entrance
B. At a readily accessible location either outside or nearest the point of
entrance of the service conductors
C. Only on the roof of the building
D. At the farthest point from the service entrance
2
,Answer: B. At a readily accessible location either outside or nearest
the point of entrance of the service conductors
Rationale: The NEC places strong emphasis on accessibility and
limiting the distance that unprotected service conductors travel within
a building. Service disconnecting means are generally required to be
installed at a readily accessible location either outside or inside nearest
the point of entrance of the service conductors.
4. A service has multiple disconnecting means permitted by the NEC.
Which arrangement best reflects the intent of the service-
disconnecting requirements?
A. Unlimited disconnects may be installed in different buildings
B. The permitted disconnects should be grouped together in the required
location
C. Each disconnect must be installed in a separate room
D. Disconnects may be scattered throughout the building
Answer: B. The permitted disconnects should be grouped together
in the required location
Rationale: Where multiple service disconnects are permitted, the NEC
requires them to be grouped in accordance with the applicable service-
disconnect provisions. Grouping allows emergency personnel and
qualified persons to identify and disconnect the service efficiently.
5. A service disconnect is installed in a locked electrical room. The
room can only be accessed by a key held by a building manager
who is frequently absent. Which concern is most directly raised by
this arrangement?
A. The service conductors are too large
B. The disconnect may not be readily accessible as required
3
, C. The grounded conductor is oversized
D. The meter is installed too low
Answer: B. The disconnect may not be readily accessible as required
Rationale: Service disconnecting means are generally required to be
readily accessible. An arrangement requiring unavailable personnel or
unreasonable effort to obtain access can defeat the safety purpose of
the disconnecting means.
6. Which conductor is normally connected to the grounded terminal
of service equipment in a grounded AC service?
A. Equipment grounding conductor only
B. Grounded circuit conductor
C. Equipment bonding jumper only
D. Grounding electrode conductor only
Answer: B. Grounded circuit conductor
Rationale: In a grounded service, the grounded circuit conductor is
connected to the grounded service conductor terminal and is bonded to
the service equipment enclosure through the main bonding connection
at the service disconnecting means. This establishes the effective fault-
current path while maintaining the required service grounding
arrangement.
7. In a typical grounded service, where is the main system bonding
jumper installed?
A. At every downstream panelboard
B. At the service disconnecting means
C. At every branch-circuit receptacle
D. Only at the grounding electrode
4