1. Under current Kansas State Fire Marshal requirements, what is the
statewide status of fire alarm company licensing?
A. All fire alarm companies must obtain a state contractor license
B. Fire alarm companies are exempt from all registration requirements
C. Kansas does not currently license fire alarm companies, but registration with
the State Fire Marshal is required
D. Only companies performing residential work must be licensed
Answer: Kansas does not currently license fire alarm companies, but registration
with the State Fire Marshal is required
Rationale: The Kansas State Fire Marshal states that fire alarm and sprinkler
companies are not licensed by the state at this time, but registration with the
Office is required.
, 2. A Kansas fire alarm contractor is preparing a project in a jurisdiction that
requires a local specialty fire alarm qualification. Which principle is most
important?
A. State registration automatically overrides local requirements
B. Local requirements are irrelevant if NFPA 72 is followed
C. The contractor must satisfy applicable state requirements and any additional
jurisdictional requirements
D. Only the equipment manufacturer's requirements apply
Answer: The contractor must satisfy applicable state requirements and any
additional jurisdictional requirements
Rationale: Local authorities can impose contractor qualification and permitting
requirements within their jurisdiction.
3. Which standard is the primary installation, testing, and maintenance
standard for fire alarm and signaling systems?
A. NFPA 13
B. NFPA 20
C. NFPA 72
D. NFPA 70E
Answer: NFPA 72
Rationale: NFPA 72 is the National Fire Alarm and Signaling Code and addresses
fire alarm and signaling system installation, performance, inspection, testing,
and maintenance.
4. Which document is most directly concerned with electrical wiring methods
for fire alarm systems?
A. NFPA 101
B. NFPA 70, National Electrical Code
C. NFPA 25
D. NFPA 13R
,Answer: NFPA 70, National Electrical Code
Rationale: The NEC establishes electrical installation requirements, while NFPA
72 provides fire alarm and signaling system requirements.
5. A fire alarm control unit has a 24-VDC nominal power supply. A notification
circuit draws 3.2 A at full alarm load. If the circuit voltage drops to 20.4 V at
the last appliance, what is the principal engineering concern?
A. Excessive detector sensitivity
B. Incorrect alarm signal coding
C. Voltage drop causing appliances to operate below their required voltage
D. Excessive smoke detector spacing
Answer: Voltage drop causing appliances to operate below their required
voltage
Rationale: Notification appliances must receive sufficient voltage under worst-
case operating conditions. Voltage-drop calculations are therefore critical.
6. Which condition generally represents a supervisory signal rather than an
alarm signal?
A. Smoke detector activation
B. Manual fire alarm box activation
C. Sprinkler control valve moved from its normal position
D. Automatic heat detector activation
Answer: Sprinkler control valve moved from its normal position
Rationale: A supervised fire protection component that changes from its normal
condition typically generates a supervisory signal.
7. What is the principal function of an end-of-line device on a supervised
initiating or notification circuit?
A. Increase circuit voltage
B. Amplify the alarm signal
, C. Permit the control unit to monitor circuit integrity
D. Reduce detector sensitivity
Answer: Permit the control unit to monitor circuit integrity
Rationale: End-of-line devices establish the expected electrical condition of a
supervised circuit and allow abnormal conditions such as opens to be detected.
8. A conventional initiating device circuit has an open conductor between the
control unit and the end-of-line resistor. What should the control unit
normally indicate?
A. Alarm
B. Supervisory
C. Trouble
D. Normal
Answer: Trouble
Rationale: An open on a supervised circuit changes its electrical condition and
normally results in a trouble indication rather than an alarm.
9. Why is polarity particularly important when installing polarized notification
appliances?
A. It determines detector spacing
B. It determines smoke sensitivity
C. Incorrect polarity can prevent the appliances from operating correctly
D. It changes the initiating device classification
Answer: Incorrect polarity can prevent the appliances from operating correctly
Rationale: Polarized notification appliances depend on proper circuit polarity for
correct operation and supervision.
10.What is the primary purpose of a fire alarm system's secondary power
supply?