1. A hydronic heating system has a design flow of 60 gpm and a total system
pressure drop of 18 ft of head. Which pump characteristic is most
appropriate for selecting the circulator?
A. 60 gpm at 18 psi
B. 60 gpm at 18 ft of head
C. 18 gpm at 60 ft of head
D. 60 psi at 18 gpm
Answer: 60 gpm at 18 ft of head
Rationale: Pump selection requires the design flow rate and the required total
dynamic head. Head and pressure are related but are not numerically
interchangeable; 18 ft of water is substantially less than 18 psi.
, 2. A variable-air-volume system is experiencing excessive fan energy use at
low load because the supply fan remains near full speed. Which control
strategy provides the greatest potential energy reduction?
A. Increase duct static pressure
B. Install a constant-volume damper
C. Use a variable-frequency drive with static-pressure reset
D. Increase the fan motor horsepower
Answer: Use a variable-frequency drive with static-pressure reset
Rationale: A VFD allows fan speed to decrease with load, while static-pressure
reset prevents the system from maintaining unnecessarily high duct pressure.
3. A refrigeration compressor has a normal suction pressure but an unusually
high discharge pressure and elevated condensing temperature. Which
condition is most likely?
A. Low refrigerant charge
B. Excessive condenser heat rejection
C. Dirty condenser or inadequate condenser airflow
D. Excessive evaporator airflow
Answer: Dirty condenser or inadequate condenser airflow
Rationale: Restricted condenser airflow or a fouled condenser reduces heat
rejection and causes condensing pressure and discharge temperature to rise.
4. When calculating the heating load of a building, which condition generally
produces the greatest increase in transmission heat loss?
A. Increasing insulation R-value
B. Reducing exposed surface area
C. Increasing the temperature difference across the building envelope
D. Reducing window area
Answer: Increasing the temperature difference across the building envelope
,Rationale: Transmission heat loss is directly proportional to the temperature
difference between indoors and outdoors and inversely proportional to the
thermal resistance of the envelope.
5. A boiler has a rated input of 1,500,000 Btu/h and an operating efficiency of
82%. Approximately how much useful heat is produced?
A. 1,230,000 Btu/h
B. 1,500,000 Btu/h
C. 1,830,000 Btu/h
D. 820,000 Btu/h
Answer: 1,230,000 Btu/h
Rationale: Useful output = input × efficiency. Therefore, 1,500,000 × 0.82 =
1,230,000 Btu/h.
6. A mechanical room contains a gas-fired appliance and has inadequate
combustion air. What is the most serious potential consequence?
A. Reduced duct velocity
B. Incomplete combustion and carbon monoxide production
C. Increased evaporator pressure
D. Reduced pump head
Answer: Incomplete combustion and carbon monoxide production
Rationale: Insufficient combustion air can cause incomplete combustion,
producing carbon monoxide and creating a serious life-safety hazard.
7. What is the primary purpose of a refrigerant receiver in a refrigeration
system?
A. Increase compressor displacement
B. Store liquid refrigerant
C. Remove moisture from oil
D. Increase evaporator superheat
, Answer: Store liquid refrigerant
Rationale: A receiver provides a controlled location for storing liquid refrigerant,
particularly in systems with varying operating conditions or pump-down
arrangements.
8. A heating system has a 20°F temperature difference between supply and
return water and transfers 2,000,000 Btu/h. Approximately what flow is
required?
A. 100 gpm
B. 150 gpm
C. 200 gpm
D. 250 gpm
Answer: 200 gpm
Rationale: Using Q = 500 × GPM × ΔT, GPM = 2,000,000 ÷ (500 × 20) = 200 gpm.
9. A centrifugal pump begins cavitating after a system modification. Which
condition should be investigated first?
A. Excessive motor voltage
B. Insufficient net positive suction head available
C. Excessive discharge pressure only
D. Oversized expansion tank
Answer: Insufficient net positive suction head available
Rationale: Cavitation occurs when local pressure falls below the liquid's vapor
pressure. Insufficient NPSH available is a primary cause.
10.In a direct-expansion evaporator, excessive superheat at the evaporator
outlet most commonly indicates:
A. Excessive refrigerant feed
B. Starved evaporator