Pole steps - ANSWER ✔✔135 deg apart
No less than 9' to first step
36" space between steps on same side
Vertical clearance between the lowest energized part of equipment
cut-outs or line disconnects and 0-750 volt conductors attached to: -
ANSWER ✔✔4' from cross arms and extended racks
6' from 3 spool rack
Reference Rules 58.1C, and 58.3A
,Pole risers - ANSWER ✔✔• Priority 1 - Keep riser(s) outside of the
climbing space.
• Priority 2 - Place on opposite side of pole
from oncoming traffic, if not possible to maintain climbing space place
the risers facing traffic.
• Priority 3 - Best remaining location to accommodate direction of
conduit, if riser(s) are to be
placed on the street side of the pole, the distance between the face of
the riser and the curb face
should preferably be 18" if possible, but no less than 12".
High volt signs - ANSWER ✔✔approximately 30" below the lowest
line conductor
energized in excess of 750 volts
6" below the equipment and above all secondary conductors and com
approximately 30 inches below the lowest exposed energized portion of
the pothead.
,Guy make ups - ANSWER ✔✔YBOG
Yellow- 1/4" 2375
Black- 5/16"
Orange 3/8" 5400
Green 7/16" 7250
Service make ups - ANSWER ✔✔#4 orange ORYOG
#2 red
1/0 yellow
3/0 orange
336 green
Bullet colors - ANSWER ✔✔8 sol brown
6 sol green
34.5 mid span lateral - ANSWER ✔✔Min 35' from pole
Reduced tension span not to exceed 55'
Line conductor sizes for mid-span clamp 3/0 ASCR to 795 AAC and 1/0
to 350 CU
COPYRIGHT©NINJANERD 2025/2026. YEAR PUBLISHED 2026. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE. PRIVACY
STATEMENT. ALL RIGHTS RESERVED
3
, Max dead end strain on clamp not to exceed 1000 lbs. max wire size of
477 ASCR
& 4/0 CU at reduced tension
Single cross arm - ANSWER ✔✔Carriage bolt w nuts
Mechanical gain
18" da bolt. X2 nuts/washers
V brace 60"
12" machine bolt x 1 washer/nut
Double cross arm - ANSWER ✔✔Boney arm : has all the bolts a d v
brace
Regular arm with mac gain
Center 2 nuts 2 washers