Texas Fire Alarm Exam Questions and Answers | Latest 2026 Update
Q: When may the manual testing frequency be extended to ANNUALLY?
Answer:
If automatic testing is performed AT LEAST weekly by a remote fire alarm control
unit. In non-household applications, when shall the sensitivity of smoke detectors be
tested? Within one year or installation and alternating years thereafter. However, if
the second sensitivity test indicates that the detector has stayed within a healthy
range, the time between calibration tests may be extended for up to 5 years. How
long does a monitoring facility have to notify clients of a change in service provider?
30 days, in writing In areas in which more than two visual notification appliances can
be seen, they shall be ______________. Synchronized. This is to avoid triggering
epileptic seizures. How should visible notification appliances be mounted when
ceiling height exceeds 30ft'? The appliances should be suspended at or below 30ft. If
this is not possible, wall mounted appliances must be used. The installation of fire
devices shall comply with which 9 rules? 1. Equipment shall not be located where
ambient condition are outside of manufacturer's recommendations. 2. Equipment
shall not be located within spaces where temperatures fall below 40f and above 100f.
3. Equipment shall not be located on any mounting surface that will become
considerably warmer or cooler than the room 4. Equipment within a 20ft path of a
cooking appliance must be of the photo-electric type or have a means of alarm
silencing. 5. Equipment shall not be installed within a 36in horizontal path of a
bathroom containing a shower or tub. 6. Equipment shall not be installed within a
36in horizontal path of the supply registers heating/cooling systems.
, Q: 7. Equipment shall not be installed within a 36in horizontal path from the tip of a
ceiling fan blade 8. Smoke rising up a stairway must not be blocked by a door or
obstruction 9. For stairways up from a basement, equipment shall he placed on
the basement ceiling near to the entry to the stairs. Voltage Drop Formula E = I
x R Return systems having capacity greater than 15,000 cubic ft/ min and
serving more than one story must have detectors where?
Answer:
On the supply side downstream of filter and ahead of branch connections AND the
return side of each story before connection to common return When shall an off
normal signal for a tamper switch initiate? During the first 2 revolutions of the hand
wheel or 1/5 of the distance of the valve apparatus from normal position. Expansion
rate of high expansion foam expansion up to 1000 x original volume Principle use of
heat detectors Respond to the convected thermal energy of a fire What is
multiplexing? signaling method that uses simultaneous transmission and reception of
multiple signals on the same SLC or transmission channel - can positively ID each
individual signal How does Photoelectric Light Obscuration Smoke Detectors work?
Smoke particles enter the light path, light is obscured from the photosensitive device
causing the detector to respond. Detector comprised of small diameter tubing
installed on the ceiling or high on the walls of a protected area Line type pneumatic
rate of rise tubing
Q: When may the manual testing frequency be extended to ANNUALLY?
Answer:
If automatic testing is performed AT LEAST weekly by a remote fire alarm control
unit. In non-household applications, when shall the sensitivity of smoke detectors be
tested? Within one year or installation and alternating years thereafter. However, if
the second sensitivity test indicates that the detector has stayed within a healthy
range, the time between calibration tests may be extended for up to 5 years. How
long does a monitoring facility have to notify clients of a change in service provider?
30 days, in writing In areas in which more than two visual notification appliances can
be seen, they shall be ______________. Synchronized. This is to avoid triggering
epileptic seizures. How should visible notification appliances be mounted when
ceiling height exceeds 30ft'? The appliances should be suspended at or below 30ft. If
this is not possible, wall mounted appliances must be used. The installation of fire
devices shall comply with which 9 rules? 1. Equipment shall not be located where
ambient condition are outside of manufacturer's recommendations. 2. Equipment
shall not be located within spaces where temperatures fall below 40f and above 100f.
3. Equipment shall not be located on any mounting surface that will become
considerably warmer or cooler than the room 4. Equipment within a 20ft path of a
cooking appliance must be of the photo-electric type or have a means of alarm
silencing. 5. Equipment shall not be installed within a 36in horizontal path of a
bathroom containing a shower or tub. 6. Equipment shall not be installed within a
36in horizontal path of the supply registers heating/cooling systems.
, Q: 7. Equipment shall not be installed within a 36in horizontal path from the tip of a
ceiling fan blade 8. Smoke rising up a stairway must not be blocked by a door or
obstruction 9. For stairways up from a basement, equipment shall he placed on
the basement ceiling near to the entry to the stairs. Voltage Drop Formula E = I
x R Return systems having capacity greater than 15,000 cubic ft/ min and
serving more than one story must have detectors where?
Answer:
On the supply side downstream of filter and ahead of branch connections AND the
return side of each story before connection to common return When shall an off
normal signal for a tamper switch initiate? During the first 2 revolutions of the hand
wheel or 1/5 of the distance of the valve apparatus from normal position. Expansion
rate of high expansion foam expansion up to 1000 x original volume Principle use of
heat detectors Respond to the convected thermal energy of a fire What is
multiplexing? signaling method that uses simultaneous transmission and reception of
multiple signals on the same SLC or transmission channel - can positively ID each
individual signal How does Photoelectric Light Obscuration Smoke Detectors work?
Smoke particles enter the light path, light is obscured from the photosensitive device
causing the detector to respond. Detector comprised of small diameter tubing
installed on the ceiling or high on the walls of a protected area Line type pneumatic
rate of rise tubing