S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 SPRINKLER TEST |UPDATED
QUESTIONS AND VERIFIED ANSWERS
GRADED A+
QUESTIONS & ANSWERS
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS.. ANSWER - OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS.. ANSWER - 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY
WITH REQUIREMENTS.. ANSWER - IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE.. ANSWER
-1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.. ANSWER - 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS.. ANSWER - 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE
DEPT.. ANSWER - OWNER OF THE BUILDING
,IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.. ANSWER -
30
WHAT DOES "OOS" STAND FOR?. ANSWER - OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER.
ANSWER - TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE
AND ANY SECTIONAL VALVES.. ANSWER - MASTER FIRE SUPPRESSION
PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER.. ANSWER - DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________.. ANSWER - NO IMPAIRMENT
WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.. ANSWER - MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE.. ANSWER -
RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.. ANSWER - WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.. ANSWER - BLUE
, THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS.. ANSWER - INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL
ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED..
ANSWER - IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING.. ANSWER - 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED
NEAR THE ____________.. ANSWER - MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF
THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS..
ANSWER - RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF
AND COURT PROCEEDINGS.. ANSWER - REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS:. ANSWER - REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE
STANDPIPE AND SPRINKLER SYSTEMS.. ANSWER - MASTER FIRE
SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.. ANSWER - 30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED.. ANSWER - 96
S12 SPRINKLER TEST |UPDATED
QUESTIONS AND VERIFIED ANSWERS
GRADED A+
QUESTIONS & ANSWERS
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS.. ANSWER - OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS.. ANSWER - 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY
WITH REQUIREMENTS.. ANSWER - IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE.. ANSWER
-1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.. ANSWER - 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS.. ANSWER - 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE
DEPT.. ANSWER - OWNER OF THE BUILDING
,IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.. ANSWER -
30
WHAT DOES "OOS" STAND FOR?. ANSWER - OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER.
ANSWER - TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE
AND ANY SECTIONAL VALVES.. ANSWER - MASTER FIRE SUPPRESSION
PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER.. ANSWER - DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________.. ANSWER - NO IMPAIRMENT
WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.. ANSWER - MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE.. ANSWER -
RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.. ANSWER - WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.. ANSWER - BLUE
, THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS.. ANSWER - INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL
ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED..
ANSWER - IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING.. ANSWER - 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED
NEAR THE ____________.. ANSWER - MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF
THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS..
ANSWER - RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF
AND COURT PROCEEDINGS.. ANSWER - REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS:. ANSWER - REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE
STANDPIPE AND SPRINKLER SYSTEMS.. ANSWER - MASTER FIRE
SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.. ANSWER - 30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED.. ANSWER - 96