COMPLETE EPA SECTION 608 TECHNICIAN CERTIFICATION STUDY
GUIDE WITH VERIFIED QUESTIONS, DETAILED RATIONALES, CORE
CERTIFICATION, TYPE I, TYPE II & TYPE III REFRIGERANT HANDLING,
REFRIGERANT RECOVERY & RECYCLING, LEAK DETECTION, EPA
REGULATIONS, OZONE PROTECTION, HVAC SAFETY & LICENSING EXAM
PREP
Question 1
What is the primary environmental concern associated with
chlorofluorocarbon (CFC) refrigerants?
A. They contribute to acid rain formation
B. They cause immediate respiratory toxicity in humans
C. They deplete stratospheric ozone through chlorine release
D. They increase ground-level ozone pollution
Correct Answer: C
Rationale: CFCs release chlorine in the stratosphere, destroying ozone
catalytically.
Question 2
Which refrigerant classification has zero ozone depletion potential
(ODP)?
A. CFC
B. HCFC
,C. Halon
D. HFC
Correct Answer: D
Rationale: HFCs contain no chlorine or bromine → zero ODP.
Question 3
Under EPA Section 608, what is the maximum allowable annual leak
rate for commercial refrigeration systems containing more than 50
pounds of refrigerant?
A. 10%
B. 15%
C. 25%
D. 35%
Correct Answer: D
Rationale: Commercial refrigeration >50 lbs: 35% threshold. Other
appliances >50 lbs: 15%.
Question 4
What does the term "recovery" mean in the context of EPA Section 608
refrigerant management?
A. Processing refrigerant to meet ARI 700 virgin purity specifications
B. Cleaning refrigerant on-site for immediate reuse in the same system
C. Removing refrigerant from a system and storing it in an external
container
D. Destroying refrigerant through high-temperature incineration
,Correct Answer: C
Rationale: Recovery = removal and external storage without
testing/processing.
Question 5
Which color coding is standard for the compound (low-side) gauge on a
refrigerant manifold gauge set?
A. Red
B. Yellow
C. Blue
D. Green
Correct Answer: C
Rationale: Blue = low side; Red = high side; Yellow = center service port.
Question 6
What is the required evacuation level for a high-pressure appliance
containing less than 200 pounds of R-22 when using recovery
equipment manufactured on or after November 15, 1993?
A. 0 inches of Hg vacuum
B. 4 inches of Hg vacuum
C. 10 inches of Hg vacuum
D. 15 inches of Hg vacuum
Correct Answer: B
Rationale: For <200 lbs of HCFC-22 → 4 inches Hg vacuum.
, Question 7
Which of the following is NOT an acceptable method for leak detection
in refrigeration systems?
A. Electronic ultrasonic leak detector
B. Halide torch producing a green flame
C. Compressed oxygen pressurization with soap bubbles
D. Fluorescent dye injection with UV light inspection
Correct Answer: C
Rationale: Compressed oxygen + oil = explosion hazard. Only nitrogen is
acceptable.
Question 8
What is the primary purpose of a purge unit on a low-pressure
centrifugal chiller?
A. To recover refrigerant during system shutdown
B. To remove non-condensable gases and moisture that leak into the
system
C. To compress refrigerant vapor for the condenser
D. To regulate evaporator water flow rate
Correct Answer: B
Rationale: Purge units remove air/moisture that enters below-
atmospheric chillers.
Question 9
According to ASHRAE Standard 34, how are refrigerants classified
regarding toxicity?