Content preview

1|Page



FDNY COF P-98 EXAM | {LATEST 2026/ 2027
UPDATE} COMPLETE ACTUAL AND AUTHENTIC
EXAM | BRAND NEW!


1.- Where generally *Fuel-oil is used in buildings?* What purposes?*
......ANSWER......Is used in *Stationary Equipments*,
Two purposes:
a) *Fuel Emergency Generators*
b) *Fuel Equipment used to heat the building*


2.- What *COF is required* to supervise the *Fuel-oil transfer in the
building from one floor to another?* ......ANSWER......*P-98 and
maintain all qualifications and comply w/ requirements applicable to
such certificate holder*
*The P-98 COF is premise-related*


3.- The use of the word *should* refers to: ......ANSWER......*Polices,
procedures and / or best practices recommended by the FDNY*


4.- The use of the word *shall* refers to: ......ANSWER......*Requirement
of the Fire Code or the FDNY*


5.- *Supervision of Fuel-Oil Piping & Storage Operation*


pg. 1

,2|Page


Shall be under the *GENERAL SUPERVISION* of P-98:
......ANSWER......*A stationary fuel-oil storage tank, related piping, that
is installed on the lowest floor of the building and transfer fuel-oil
through piping to another stationary fuel-oil storage tank, or fuel
burning equipment, installed above such floor*


6.- *Supervision of Fuel-Oil Piping & Storage Operation*
Shall be under the *PERSONAL SUPERVISION* of P-98 COF shall be?
......ANSWER......*Periodic Inspection and Testing of tanks and piping*


7.- *Maintenance Requirements*
Fuel-oil storage tanks and piping *shall be inspected* for any evidence
of leaks? ......ANSWER......*Weekly*


8.- *Maintenance Requirements*
Fuel-oil storage tanks *shall have their float switches tested* to ensure
that they are in good working order at least? ......ANSWER......*Weekly*


9.- *Licences & Certificates*
*No* oil burning equipment *may operated until?* ......ANSWER......a)
*Certificate of Compliance* has been issued by *NYCDOB*
b) *Air pollution control code* requirements *NYCDEP*
c) *Permit for the Storage & use of fuel-oil* issued by *FDNY*




pg. 2

,3|Page


10.- *Licences & Certificates*
Pursuant to the *New NYC Fire Code & Mechanical Codes* stated that?
......ANSWER......*The COF is required for all existing and new buildings
where fuel is being transported from the lowest levels to tanks or
equipment on upper floors*


11.- *Oil Circulation in the System*
Diagram of:
*Oil Circulation from the Tank at the LOWEST floor of a building to the
burner on the floor above such floor through the pump*
......ANSWER......


12.- *Oil Circulation in the System*
What the *oil storage tank* do? ......ANSWER......*Provides the supply
of oil for combustion in the oil burner. It's inside a dike. In case of leak
the diked area will contain the oil.*


13.- *Oil Circulation in the System*
How is the #2 fuel-oil in its *normal condition*? ......ANSWER......*Is
thin and light and is easily pumped through the circulation system.*


14.- *Oil Circulation in the System*
*What the suction pump do?* ......ANSWER......*Circulates the oil
throughout the system. Dirt and sediment are present in the fuel-oil
coming from the oil storage tank. The oil filter removes most of these


pg. 3

, 4|Page


contaminants from the oil before the oil reaches the burner's
strainer.*


15.- *Oil Circulation in the System*
How many inches has to be the *SUCTION LINE?* ......ANSWER......*6
inches from the bottom of the tank for sediments not to be absorbed*


16.- *Oil Circulation in the System*
What is the *vacuum gauge?* ......ANSWER......*A device that
measures pressure below atmospheric pressure.*


17.- *Oil Circulation in the System*
*Excessive vacuum readings* means? ......ANSWER......*Indicate that
there is an obstruction in the suction line (such as dirty oil strainer)
when this occurs the flow of oil can be stopped by closing the shut-off
valve.*


18.- *Oil Circulation in the System*
Closing the *shut-off valve.?* ......ANSWER......Flow of oil *STOP*
*This permits the operator to clean the filter/strainer or to perform
other maintenance*


21.- *Oil Circulation in the System*




pg. 4

Document information

Uploaded on
May 16, 2026
Number of pages
44
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers
$20.09

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
AceExam1
3.5
(11)
Sold
47
Followers
1
Items
3714
Last sold
2 days ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions