⩥ Which ANSI/IEEE standard covers SF6 circuit breakers? Answer:
C37.04


⩥ You measure the winding resistance of a 12.4kV, 1000kVA, Delta-
Delta connected transformer with a 100A test set. H1-H2 measures 42.0
microhms, H2-H3 measures 41.9 microhms, and H3-H1 measures 84.0
microhms. What can you conclude from these readings? Answer: One
phase of the transformer is open.


⩥ When monitoring for entries involving a decent into atmospheres that
may be stratisfied, the envelope should be tested at a distance of
approximately _____ feet in the direction of travel and to each side.
Answer: 4


⩥ The transformer manufacturer should be consulted if winding-
resistance test values vary by more than _____ percent from factory test
values or between adjacent phases according to NETA acceptance
testing standards. Answer: 2

,⩥ A DC shunt motor should never be operated: Answer: with the field
circuit open


⩥ What is the expected torque (pound-feet) value of a 3/8" Grade 5 bolt?
Answer: 20


⩥ The generally accepted limits of deviation from the nominal 60Hz
utility power frequency is: Answer: .50Hz


⩥ Power Factor testing is least effective on which of the following?
Answer: MV Cable


⩥ Which of the following insulating liquid tests is optional when
maintenance testing a 13.2kV-4.16kV 1500kVA transformer with
silicone fluid per NETA standards? Answer: ASTM D1298


⩥ Panelboards equipped with snap switches of rating 30 amps or less
shall be provided with over-current protection of not more than _____ .
Answer: 200 amps


⩥ Underground service conductors between the terminals of service
equipment and service lateral or underground service conductors are
termed as _____ . Answer: Service Entrance Conductors

,⩥ What is a dual element fuse used for? Answer: Operate with a
temporary overload


⩥ The full-load current for a single-phase alternating current 115 volt, 1
horsepower motor is which of the following: Answer: 16 A


⩥ Infrared surveys should be performed during periods of maximum
possible loading but not less than _____ % of rated load of the electrical
equipment being inspected. Answer: 40


⩥ Decreasing the opening time of the overcurrent protective device will
decrease Arc-Flash hazards. Answer: true


⩥ In a wye connected system, without neutral grounding, zero sequence
currents are: Answer: zero


⩥ When evaluating insulation test results on a medium-voltage, air-
magnetic circuit breaker, what quantity is evaluated? Answer: watts-loss


⩥ In accordance with NETA and IEEE standards, the correct acceptance
test voltage (dc) for 35KV rated EPR 133% insulation level cable is?
Answer: 124kV

, ⩥ Calculate the circuit time constant of an inductor having resistance
value of 100 ohms and an inductance value of 4 Henry: Answer: 0.04
sec
T=L/R


⩥ Transformer polarity: Answer: Is of concern when multiple sets of
primary and secondary windings are interconnected


⩥ Identify the least reliable power system arrangement: Answer: Radial
w/ Primary Selectivity


⩥ The hot collar bushing test should be performed using which of the
following test modes? Answer: UST
GST
GST-g


⩥ R rated fuses are used for: Answer: Protection for motors
R-rated fuses provide required short-circuit protection for medium
voltage motors, motor controllers and associated circuitry. Relays
provide both overload protection and locked rotor protection to the
motor.


⩥ Which of the following would be a factor in choosing between 100%,
133%, and 173% Medium voltage cable for a power system? Answer:
Ground Fault protection

Información del documento

Subido en
7 de mayo de 2026
Número de páginas
38
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$12.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
Vendido
31
Seguidores
1
Artículos
14355
Última venta
5 horas hace


Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes