Nicet level 1 Study Guide Exam
Questions & Answers (Grade A+)
When testing a water level supervisory switch serving a pressure
tank a signal shall indicate if the water level _____________from
the required level


(NFPA 72, Table 14.4.3.2 17 (j) (4) -
correct answer ✅rises or falls over 3 inches


If combination audible/visible appliances are installed the location
of the installed appliance shall be determined by the requirements
of _______.


(Nfpa 72 18.4.8.1) -
correct answer ✅the visible appliance


What is the maximum number of 12 gauge THHN wires that can be
installed in 1" EMT?


(Nec Annex C tables) -
correct answer ✅26

,Nicet level 1 Study Guide Exam
Questions & Answers (Grade A+)
Two resistors are connected in parallel. R1 = 300 Ohms, R2 = 300
Ohms. What is their equivalent resistance? -
correct answer ✅150 ohms


A Room is 200' long and 150' wide and the 8' high ceiling is smooth
and flat. A spot type heat detector has been selected that is listed
for a 50' maximum spacing between detectors. According to NFPA
72 how many detectors will be needed to protect this room?


x = -
correct answer ✅12


According to NFPA 72 the minimum number of restorable fixed
temperature spot type heat detectors that must be tested during
each annual test is?


(NFPA 72 14.4.4.5.1) -
correct answer ✅Two detectors or more on each initiating device
circuit


According to NFPA 72 how many spot type heat detectors are
required for a space that is 80' long and 55 floor wide with a

,Nicet level 1 Study Guide Exam
Questions & Answers (Grade A+)
smooth 10' ceiling? the detector is listed for a maximum space
between detectors of 30' -
correct answer ✅6


What color code requirement for a spot type heat detector rated at
200 ゚ F -
correct answer ✅White (NFPA 72, Table 17.6.2.1)


Unless otherwise recommended by the manufacturers published
instructions single and multiple stations smoke alarms installed in
one and 2 family dwellings shall be replaced every -
correct answer ✅10 years from the day-of manufacture. (NFPA 72,
14.4.7.1)


Fire alarm cables are permitted to be strapped to conduit to
support the cable -
correct answer ✅False (NEC 760.143)


Where non power limited wiring is installed exposed it must be
mechanically protected within_____of the finished floor -
correct answer ✅7' ft

, Nicet level 1 Study Guide Exam
Questions & Answers (Grade A+)
Fire-Warning equipment to be installed in residential occupancies
shall produce the audible emergency evacuation signal described in
-
correct answer ✅ANSI S3.41


According to NFPA 72, visible notification appliance for non-
sleeping areas must be mounted between ___ and ___ inches
above the finished floor -
correct answer ✅80 & 96


If system impairment occurs, the owner must be notified ___ within
___ -
correct answer ✅in writing & within 24 hours


A 20 X 20' ft room with a 20'ft high ceiling requires at a minimum a
___ ceiling mounted strobe -
correct answer ✅30 candela


According to NFPA 72, a 40 x 40'ft room or area with a 10'ft ceiling
is best covered by a ___ cd visible notification appliance, centered
on one wall. -
correct answer ✅60

Document information

Uploaded on
April 22, 2026
Number of pages
34
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers
$15.99

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Cindellera
3.9
(31)
Sold
183
Followers
3
Items
15435
Last sold
5 days ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions