Department of Buildings Licensing Test
Latest Questions & Verified Answers
(Grade A)
A listed assembly of two , three, or four insulated circuit conductors within a
NONMETALLIC jacket, an extruded thermoplastic covering, or a sealed nonmetallic
covering that can be mounted directly on the surface of walls and ceilings is the
definition for:
A) Flat conductor cable
B) Flat cable assemblies
C) Nonmetallic sheath cable
D) Concealable nonmetallic extension - correct answer Concealable nonmetallic
extension
(article 382.2)
,A group of devices that serve to govern in some predetermined manner the electric
power delivered to the apparatus to which it is connected is a ?
A) Device
B) Controller
C) Disconnect
D) Circuit breaker - correct answer Controller
(article 100)
For a service panel fed by parallel 3/0 AWG copper conductors, the copper
GROUNDING - ELECTRODE run from the service panel to the metallic water service
shall be at least size ____________ AWG
,A) 4
B) 2
C) 1/0
D) 2/0 - correct answer 2
(table 250.66)
A dry - type TRANSFORMER may be LOCATED in a suspended ceiling space where it is
not ready ACCESSIBLE if the voltage is 600 volts or less and has a maximum rating of
____________ kva
A) 10
B) 25
C) 50
D( 112 - correct answer 50
, (article 450.13 (B) )
A SERVICE head can be located no further away from the point of attachment than
____________ inches
A) 18
B) 24
C) 36
D) 48 - correct answer 24"
(article 230.54) (C) (exceptions)
ACCEPTABLE METHODS of connecting GROUNDING and BONDING conductors include
all the following, EXCEPT: