Extinguishers listed for the Class C rating shall not contain an agent that is a
conductor of ________ - ANSWER-Electricity
Dry chemical stored pressure extinguishers manufactured prior to
_____________ shall be removed from service at the next 6 year maintenance
interval or the next hydrostatic test whichever comes first - ANSWER-October
1984
Any fire extinguisher that can no longer be serviced in accordance with the
manufacturers maintenance manual is considered to be _______ and shall be
________ from service - ANSWER-obsolete, removed
Class A fires involve - ANSWER-Common Combustibles such as paper, wood,
cloth, rubber, plastics
Class B fires involve - ANSWER-Usually involve flammable liquids, greases,
tars oils, paints, alcohols, and flammable gases
Class C fires involve - ANSWER-Usually involve live electrical equipment
Class D fires involve - ANSWER-Fires involving combustible metals such as
magnesium, titanium, zirconium, sodium, and potassium.
, Class K fires involve - ANSWER-cooking appliances that involve combustible
cooking
media (vegetable or animal oils and fats).
Is a wheeled fire extinguisher considered a portable fire extinguisher? -
ANSWER-Yes
Portable fire extinguishers shall be ______ and _____ and meet all of the
requirements of one of the fire test standards indicated - ANSWER-listed and
labeled
Fire extinguishers having a gross weight not exceeding 40lbs shall be installed
so that the top of the extinguisher is no more the _______ ft above the floor -
ANSWER-5
Fire extinguishers having a gross weight greater than 40lbs shall be installed so
that the top of the extinguisher is no more the _______ ft above the floor -
ANSWER-3.5
In no case shall the clearance between the bottom of the extinguisher and the
floor be less than ______ - ANSWER-4in
HMIS, 6 year, hydrostatic test or other labels shall not be placed on what part of
the extinguisher? - ANSWER-the front
What is the minimum Class A rating for a single fire extinguisher for light and
ordinary hazard occupancy/ - ANSWER-2-A
For a 3000 sq ft facility, how many 2-A rated extinguishers would be required
for ordinary hazard occupancy? - ANSWER-2