EVITP Final Actual Exam2026/2027 Newest With
Complete Questions And Correct Detailed Answers|
Latest Version!!
The EV industry is comprised of ? .
Select one:
a.auto manufacturers
b.consumer advocacy groups
c.EV charging equipment manufacturers
d.research and standards organizations
e.all of the above - ANSWER-e. all of the above
A Level II EVSE with a rating of 32 amperes at 208 volts is
installed. What is the minimum size copper equipment
grounding conductor required to serve the installation?
,Select one:
a.10 AWG
b.8 AWG
c.6 AWG
d.4 AWG - ANSWER-a.10 AWG
Note: Section 250.122 - the EVSE will be served by a 40A
OCPD; therefore, the minimum size equipment ground will
be 10 AWG.
Additional EVSEs are to be added to an existing 120/208-
volt, 3-phase, 4-wire, 600-ampere service with 220
amperes of non-continuous load and 172 amperes of
continuous load. The EVSEs each draw 32 amperes. How
,many new EVSEs can be added to the service? (Note:
Use 1.732 for the square root of 3.)
Select one:
a.2
b.3
c.6
d.9 - ANSWER-c.6
220 A + (172 A × 1.25) = 435 A
600 A - 435 A = 165 A
165 A × 0.8 = 132 A left (due to EVSEs being continuous
loads)
, (32 × 1.732) = 55.43
132 A / 55.43 = 2.38 or 2 per phase
Total = 6 EVSEs
What is the minimum copper THHN feeder size for 12
EVSEs rated at 24 amperes on a 3-phase, 4-wire,
120/208-volt system, assuming four EVSE per phase?
(Note: Use 1.732 for the square root of 3.)
Select one:
a.250 kcmil
b.350 kcmil
Complete Questions And Correct Detailed Answers|
Latest Version!!
The EV industry is comprised of ? .
Select one:
a.auto manufacturers
b.consumer advocacy groups
c.EV charging equipment manufacturers
d.research and standards organizations
e.all of the above - ANSWER-e. all of the above
A Level II EVSE with a rating of 32 amperes at 208 volts is
installed. What is the minimum size copper equipment
grounding conductor required to serve the installation?
,Select one:
a.10 AWG
b.8 AWG
c.6 AWG
d.4 AWG - ANSWER-a.10 AWG
Note: Section 250.122 - the EVSE will be served by a 40A
OCPD; therefore, the minimum size equipment ground will
be 10 AWG.
Additional EVSEs are to be added to an existing 120/208-
volt, 3-phase, 4-wire, 600-ampere service with 220
amperes of non-continuous load and 172 amperes of
continuous load. The EVSEs each draw 32 amperes. How
,many new EVSEs can be added to the service? (Note:
Use 1.732 for the square root of 3.)
Select one:
a.2
b.3
c.6
d.9 - ANSWER-c.6
220 A + (172 A × 1.25) = 435 A
600 A - 435 A = 165 A
165 A × 0.8 = 132 A left (due to EVSEs being continuous
loads)
, (32 × 1.732) = 55.43
132 A / 55.43 = 2.38 or 2 per phase
Total = 6 EVSEs
What is the minimum copper THHN feeder size for 12
EVSEs rated at 24 amperes on a 3-phase, 4-wire,
120/208-volt system, assuming four EVSE per phase?
(Note: Use 1.732 for the square root of 3.)
Select one:
a.250 kcmil
b.350 kcmil