ALL ELECTRICAL WORKS HEREIN SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). THE EXISTING LOCAL ORDINANCES RULES & REGULATIONS OF THE MUNICIPAL ELECTRICIAN & REQUIREMENTS OF THE UTILITY COMPANY. 2. INCOMING PRIMARY SERVICE TO THE BUILDING SHALL BE 34500 , 3 PHASE , 4 WIRES 60 HZ. DISTRIBUTION WITHIN THE BUILDING SHALL BE 230V , 3 PHASE , 4 WIRES , 60 HZ. 3. ALL WIRE SHALL BE COPPER WITH AT LEAST 99% CONDUCTIVITY, 600 VOLTS INSULATION, THERMOPLASTIC INSULATED TYPE "THHN" & "THW" UNLESS OTHERWISE INDICATED, AND COLUMBIA OR PHELPS DODGE BRAND. THE MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 3.5 mm². 4. THE ELECTRICAL WIRING INSULATION SHALL BE DONE IN RIGID STEEL CONDUIT (RSC) , OR RIGID PVC CONDUIT AS SPECIFIED, CONCEALED IN CEILING, CONCRETE AND MASONRY WORKS AND IN DOUBLE WOOD WALLS. FLEXIBLE METALLIC CONDUITS SHALL BE USED WHERE REQUIRED MINIMUM SIZE FOR ALL CONDUIT SHALL BE 15 mm Ø ELECTRICAL TRADE SIZE. 5. BRAND OF CONDUITS ARE AS FOLLOWS: A. PVC - "NELTEX" BRAND OR APPROVED EQUAL. B. RSC - "NICHI" BRAND OR APPROVED EQUAL. 6. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANEL BOARDS, LIGHTING FIXTURES AND ALL NON-CURRENT CARRYING METAL PARTS SHALL BE PROPERLY CONDUCTED. GROUND WIRE MUST BE CONTINUOUS WITH GREEN INSULATION . 7. ALL SINGLE PHASE LOAD SHALL BE CONNECTED TO EFFECT A BALANCED 3 PHASE SYSTEM. 8. NO BRANCH CIRCUIT SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING. 9. ALL SERVICE EQUIPMENT SHALL BE RATED GROUNDED IN ACCORDANCE WITH THE REQUIREMENTS OF THE P.E.C 10. GENERAL USED RECEPTACLE SHALL BE RATED 10A , 250V , DUPLEX PARALLEL SLOTS AND GROUNDED TYPE RECEPTACLE SPECIAL PURPOSE OUTLET SHALL OF THE TYPE AND RATING SUIT THE EQUIPMENT. 11. FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED PLANS. INDIVIDUAL BRANCH CIRCUIT HOMERUN SHALL NOT BE COMBINED IN THE SAME CONDUITS UNLESS EXPLICITLY PROVIDED. 12. ALL ELECTRICAL INSTALLATION HEREIN SHALL BE UNDER DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN. 13. ANY DISCREPANCY IN LOCATION AND RATING OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED WITH THE ENGINEER/OWNER OR ANY OF HIS REPRES

Content preview

1. ALL ELECTRICAL WORKS HEREIN SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF
THE PHILIPPINE ELECTRICAL CODE (PEC). THE EXISTING LOCAL ORDINANCES RULES &
REGULATIONS OF THE MUNICIPAL ELECTRICIAN & REQUIREMENTS OF THE UTILITY COMPANY.

2. INCOMING PRIMARY SERVICE TO THE BUILDING SHALL BE 34500 , 3 PHASE , 4 WIRES 60 HZ. DISTRIBUTION
WITHIN THE BUILDING SHALL BE 230V , 3 PHASE , 4 WIRES , 60 HZ.

3. ALL WIRE SHALL BE COPPER WITH AT LEAST 99% CONDUCTIVITY, 600 VOLTS INSULATION,
THERMOPLASTIC INSULATED TYPE "THHN" & "THW" UNLESS OTHERWISE INDICATED, AND COLUMBIA OR
PHELPS DODGE BRAND. THE MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 3.5 mm².

4. THE ELECTRICAL WIRING INSULATION SHALL BE DONE IN RIGID STEEL CONDUIT (RSC) , OR RIGID PVC
CONDUIT AS SPECIFIED, CONCEALED IN CEILING, CONCRETE AND MASONRY WORKS AND IN
DOUBLE WOOD WALLS. FLEXIBLE METALLIC CONDUITS SHALL BE USED WHERE REQUIRED MINIMUM
SIZE FOR ALL CONDUIT SHALL BE 15 mm Ø ELECTRICAL TRADE SIZE.

5. BRAND OF CONDUITS ARE AS FOLLOWS:

A. PVC - "NELTEX" BRAND OR APPROVED EQUAL.
B. RSC - "NICHI" BRAND OR APPROVED EQUAL.

6. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANEL BOARDS, LIGHTING FIXTURES AND ALL
NON-CURRENT CARRYING METAL PARTS SHALL BE PROPERLY CONDUCTED. GROUND WIRE MUST BE
CONTINUOUS WITH GREEN INSULATION .

7. ALL SINGLE PHASE LOAD SHALL BE CONNECTED TO EFFECT A BALANCED 3 PHASE SYSTEM.

8. NO BRANCH CIRCUIT SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING.

9. ALL SERVICE EQUIPMENT SHALL BE RATED GROUNDED IN ACCORDANCE WITH THE REQUIREMENTS OF THE
P.E.C

10. GENERAL USED RECEPTACLE SHALL BE RATED 10A , 250V , DUPLEX PARALLEL SLOTS AND GROUNDED TYPE G
RECEPTACLE SPECIAL PURPOSE OUTLET SHALL OF THE TYPE AND RATING SUIT THE EQUIPMENT.

11. FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED PLANS. INDIVIDUAL BRANCH
CIRCUIT HOMERUN SHALL NOT BE COMBINED IN THE SAME CONDUITS UNLESS EXPLICITLY PROVIDED.

12. ALL ELECTRICAL INSTALLATION HEREIN SHALL BE UNDER DIRECT SUPERVISION OF A DULY LICENSED
ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN.

13. ANY DISCREPANCY IN LOCATION AND RATING OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED WITH
THE ENGINEER/OWNER OR ANY OF HIS REPRESENTATIVES AND CHANGES SHALL BE MADE ACCORDINGLY.

14. ALL MATERIAL TO BE USED AND EQUIPMENT INSTALLED SHALL BE BRAND NEW AND MUST BE OF
APPROVED TYPE FOR PARTICULAR LOCATION AND PURPOSE.

15. ALL WEATHER-EXPOSED INSTALLATIONS SHALL BE WEATHERPROOF TYPE MATERIAL.
ESPECIALLY WEATHERPROOF CONVENIENCE OUTLETS AND JUNCTION BOXES INTENDED

16. FOR EACH SPARE BRANCH CIRCUIT IN THE PANEL BOARD, PROVIDE ONE 20 mm INSIDE DIAMETER
EMPTY CONDUIT TERMINATED TO A 100 mm OCTAGONAL BOX ABOVE CEILING PROVIDE PULL WIRES IN
ALL SPARE EMPTY CONDUITS.

17. THE JOB SHALL BE EXECUTED IN THE MOST THOROUGH, PROMPT AND WORKMANLIKE MANNER,
EMPLOYING STANDARD TOOLS, EQUIPMENT, METHODS AND GOOD ENGINEERING PRACTICES. THE JOB
SHALL BE COMPLETE IN ALL ASPECTS A REQUIRED IN PLAN AND SPECIFICATIONS AND READY FOR
OPERATION.

18. ALL RECEPTACLE OUTLETS SHALL BE TAGGED WITH PANEL AND CIRCUIT NUMBER SUPPLYING THEM.

19. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OF
ALL CIRCUIT BREAKERS. EACH PANEL BOARD SHALL BE PROVIDED WITH TYPEWRITTEN CIRCUIT DIRECTORY.

20. MOUNTING HEIGHT FOR ALL DEVICES ARE AS FOLLOWS:

SWITCHES................................... 1.40 m ABOVE FINISH FLOOR LINE
CONVENIENCE OUTLETS...........0.30 m ABOVE FINISH FLOOR LINE
PANEL BOARD.............................1.80 m ABOVE FINISH FLOOR LINE




TITLE OF PROJECT: NAME AND ADDRESS OF OWNER: SHEET CONTENT: DESIGNED AND DRAWN BY: CHECKED BY: NAME OF PROFESSIONAL ELECTRICAL ENGINEER: PRC REGISTERED NO.: SHEET CONTENT:

CORTEZ, JOSHUA LURRAINE D.
JABAJA CORPORATION P.E.E. GILBERT B. HOLLMAN PTR. NO.:
ELECTRICAL SYSTEM DESIGN OF AN KM 002, GOVERNOR'S DRIVE, SANTA
LIGHTING & POWER E
LAYOUT LOPEZ, GIANCARLA C. SCALE: P.E.E. GILBERT B. HOLLMAN DATE & PLACE ISSUED:
INDUSTRIAL PLANT ROSA, LAGUNA 1
NTS TIN:

Document information

Uploaded on
March 7, 2026
Number of pages
3
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers
$8.49

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Abbyy01
3.5
(13)
Sold
98
Followers
33
Items
1337
Last sold
1 day ago


Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions