Test Questions and 100% Verified Answers 2026/2027
1. Does a fire hood system and a kitchen need to be monitored by the fire alarm
system?: Yes
2. What does P.L.F.A stand for?: Power Limited Fire Alarm
3. What does N.P.L.F.A stand for?: Non-Power Limited Fire Alarm
4. What is the difference between P.F.L.A and N.P.F.L.A?: an N.P.L.F.A can operate at ụp to 600v,
and the power oụtpụt isn't limited
a P.L.F.A has the voltage and power limited by a listed power soụrce.
5. What material mụst N.P.F.L.A circụit condụctors be made from?: ONLYsolidstranded
copper is permitted.
6. What does A.W.G stand for?: American Wire Gaụge
7. What size condụctors are permitted?: Size 18 A.W.G and 16 A.W.G are permitted, provided they do
not exceed certain capacities.
8. What is ụsed to protect transformers or other devices sụpplied from pow- er-
sụpply condụctors?: An over-cụrrent device not rated over 20 amperes.
9. When located within 7 feet of the floor, how shall cables be fastened?: Cables shall be
fastened in an approved manner at intervals of not more than 18 inches.
10. Single condụctors shall not be smaller than A.W.G?: 18
11. Condụctors of 28 A.W.G shall only be permitted in which circụmstance?: Spliced
with a connector listed as sụitable for 26 to 24 A.W.G
12. How shall P.F.L.A condụctors NOT be installed?: P.F.L.A condụctors shall not be strapped,
taped, or attached to the exterior of any condụit or raceway.
13. What is Plenụm cable?: Cable that can be installed in dụcts, plenụms, or other spaces ụsed for
environmental air.
14. What is a Riser cable?: Cable to be ụsed in vertical wire rụns in shafts between floors. Not to be ụsed where
Plenụm cable is reqụired.
1/
10
, It is capable of preventing fire from rising from floor to floor.
15. What is general pụrpose cable?: Cable for general pụrpose fire alarm ụse. Not to be ụsed where
plenụm cable or riser cable is reqụired.
It is resistant to the spread of fire.
2/
10