Operating devices shall operate at
32F to 120F
Manual actuators shall not have a force more than
40lbs
Manual actuators shall not have a movement of more than
14 inches
Instructions with pictographs and lettering shall be atleast
1/4 inches
,Pipe and fittings shall be made of
Non combustible materials
galvanized pipe and fittings
Shall not be used
During assembly examine pipe
Internally to detect and remove contaminants
Readily access means for manual actuators
Shall be located in a path of egress
Manual actuators shall be installed
No more than 48in and no less than 42in
Fusible links shall be located
, At above each cooking appliance
Fusible links shall be
12 in in front of said item
A test shall be used on pipe using
Nitrogen or dry air not exceeding normal operating pressure
Piping shall not
Be hydrostatic tested
Owners inspection
Monthly
Owners inspection records shall be retained
Semi-annually
Compliance – Texas Fire Department –
Practice Test Questions and Verified
Answers (Latest Update, Graded A)
Operating devices shall operate at
32F to 120F
Manual actuators shall not have a force more than
40lbs
Manual actuators shall not have a movement of more than
14 inches
Instructions with pictographs and lettering shall be atleast
1/4 inches
,Pipe and fittings shall be made of
Non combustible materials
galvanized pipe and fittings
Shall not be used
During assembly examine pipe
Internally to detect and remove contaminants
Readily access means for manual actuators
Shall be located in a path of egress
Manual actuators shall be installed
No more than 48in and no less than 42in
Fusible links shall be located
, At above each cooking appliance
Fusible links shall be
12 in in front of said item
A test shall be used on pipe using
Nitrogen or dry air not exceeding normal operating pressure
Piping shall not
Be hydrostatic tested
Owners inspection
Monthly
Owners inspection records shall be retained
Semi-annually