S-12 CITYWIDE SPRINKLER SYSTEMS
ACTUAL TEST PAPER 2026 QUESTIONS
WITH ANSWERS GRADED A+
⩥ RECORDS OF ALL INSPECTIONS AND MX SHALL BE
MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS.
Answer: 3
⩥ THE BUILDING OWNER SHALL ASSIGN A(N) ____________
TO COMPLY WITH REQUIREMENTS. Answer: IMPAIRMENT
COORDINATOR
⩥ REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE
THAN ________ FLOOR(S) ARE CONSIDERED PLANNED
REMOVAL FROM SERVICE. Answer: 1
⩥ SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S)
ARE CONSIDERED UNPLANNED OUT OF SERVICE
CONDITIONS. Answer: 1
⩥ NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED
SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS.
Answer: 8
,⩥ FOR UNPLANNED REMOVAL FROM SERVICE, THE COF
HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE
___________ AND THE FIRE DEPT. Answer: OWNER OF THE
BUILDING
⩥ IF A MINOR DEFECT IS OBSERVED, IT SHALL BE
CORRECTED WITHIN _________ DAYS OR IT WILL BE
CONSIDERED AN IMPAIRMENT. Answer: 30
⩥ WHAT DOES "OOS" STAND FOR? Answer: OUT OF SERVICE
⩥ OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________
AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND
FIRE COMMAND CENTER Answer: TAGS
⩥ A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN
CONTROL VALVE AND ANY SECTIONAL VALVES. Answer:
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
⩥ __________ SHALL BE POSTED ON THE TAG INDICATING
BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER.
Answer: DRAIN TEST RESULTS
⩥ GREEN TAGS INDICATE THAT __________. Answer: NO
IMPAIRMENT WAS FOUND
,⩥ GREEN TAGS WILL BE PLACED ON THE ____________.
Answer: MAIN CONTROL VALVE
⩥ SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL
HAVE A ____________ TAG PLACED ON THE MAIN CONTROL
VALVE. Answer: RED
⩥ A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE. Answer: WHITE
⩥ A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT
OF SERVICE. Answer: BLUE
⩥ THE IMPAIRMENT COORDINATOR WILL NOTIFY THE
___________ CARRIER, CENTRAL STATION AND OCCUPANTS.
Answer: INSURANCE
⩥ PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________
SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS
ARE CONDUCTED. Answer: IMPAIRMENT COORDINATOR
, ⩥ GLYCERIN NOT GREATER THAN _________ PERCENT OR
GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE
USED TO PROTECT FROM FREEZING. Answer: 50, 40
⩥ THE COF NUMBER AND SIGNATURE OF COF HOLDER
SHALL BE POSTED NEAR THE ____________. Answer: MAIN
CONTROL VALVE
⩥ __________ SHALL BE READILY AVAILABLE TO ANY
REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO BE
MAINTAINED ON SITE FOR 3 YEARS. Answer: RECORDS
⩥ FAILURE TO MAKE INSPECTIONS MAY RESULT IN
__________ OF THE COF AND COURT PROCEEDINGS. Answer:
REVOCATION
⩥ THE COF HOLDER MAY INSPECT, TEST, AND PERFORM
ROUTINE MX IF THEY HOLD THE FOLLOWING CERTS: Answer:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
⩥ A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL
FIRE STANDPIPE AND SPRINKLER SYSTEMS. Answer: MASTER
FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
ACTUAL TEST PAPER 2026 QUESTIONS
WITH ANSWERS GRADED A+
⩥ RECORDS OF ALL INSPECTIONS AND MX SHALL BE
MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS.
Answer: 3
⩥ THE BUILDING OWNER SHALL ASSIGN A(N) ____________
TO COMPLY WITH REQUIREMENTS. Answer: IMPAIRMENT
COORDINATOR
⩥ REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE
THAN ________ FLOOR(S) ARE CONSIDERED PLANNED
REMOVAL FROM SERVICE. Answer: 1
⩥ SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S)
ARE CONSIDERED UNPLANNED OUT OF SERVICE
CONDITIONS. Answer: 1
⩥ NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED
SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS.
Answer: 8
,⩥ FOR UNPLANNED REMOVAL FROM SERVICE, THE COF
HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE
___________ AND THE FIRE DEPT. Answer: OWNER OF THE
BUILDING
⩥ IF A MINOR DEFECT IS OBSERVED, IT SHALL BE
CORRECTED WITHIN _________ DAYS OR IT WILL BE
CONSIDERED AN IMPAIRMENT. Answer: 30
⩥ WHAT DOES "OOS" STAND FOR? Answer: OUT OF SERVICE
⩥ OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________
AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND
FIRE COMMAND CENTER Answer: TAGS
⩥ A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN
CONTROL VALVE AND ANY SECTIONAL VALVES. Answer:
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
⩥ __________ SHALL BE POSTED ON THE TAG INDICATING
BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER.
Answer: DRAIN TEST RESULTS
⩥ GREEN TAGS INDICATE THAT __________. Answer: NO
IMPAIRMENT WAS FOUND
,⩥ GREEN TAGS WILL BE PLACED ON THE ____________.
Answer: MAIN CONTROL VALVE
⩥ SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL
HAVE A ____________ TAG PLACED ON THE MAIN CONTROL
VALVE. Answer: RED
⩥ A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE. Answer: WHITE
⩥ A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT
OF SERVICE. Answer: BLUE
⩥ THE IMPAIRMENT COORDINATOR WILL NOTIFY THE
___________ CARRIER, CENTRAL STATION AND OCCUPANTS.
Answer: INSURANCE
⩥ PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________
SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS
ARE CONDUCTED. Answer: IMPAIRMENT COORDINATOR
, ⩥ GLYCERIN NOT GREATER THAN _________ PERCENT OR
GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE
USED TO PROTECT FROM FREEZING. Answer: 50, 40
⩥ THE COF NUMBER AND SIGNATURE OF COF HOLDER
SHALL BE POSTED NEAR THE ____________. Answer: MAIN
CONTROL VALVE
⩥ __________ SHALL BE READILY AVAILABLE TO ANY
REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO BE
MAINTAINED ON SITE FOR 3 YEARS. Answer: RECORDS
⩥ FAILURE TO MAKE INSPECTIONS MAY RESULT IN
__________ OF THE COF AND COURT PROCEEDINGS. Answer:
REVOCATION
⩥ THE COF HOLDER MAY INSPECT, TEST, AND PERFORM
ROUTINE MX IF THEY HOLD THE FOLLOWING CERTS: Answer:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
⩥ A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL
FIRE STANDPIPE AND SPRINKLER SYSTEMS. Answer: MASTER
FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)