NICET Sample Exam | NICET Fire Alarm Sample Exam Questions And Answers 2023
NICET Sample Exam | NICET Fire Alarm Sample Exam Questions And Answers 2023 
Secondary power for remote supervising station systems shall be capable of normal operation for ___ hours and then operate the system in alarm for ___ minutes? 24 / 5 
 
A fire alarm system which serves contiguous or noncontiguous properties under one ownership is considered? Proprietary system 
 
An initiating device which is destroyed as a result of operation is what type? Nonrestorable 
 