Journeyman Electrician Practice Test Questions
and Answers
Save
Terms in this set (50)
A 440 volts motor has a 40 amperes
full load current of 34
amperes. what size The rating of disconnecting means is 115% of full load
disconnecting means is current.34 * 1.15 = 39.1 amperes.The nearer rating is 40
required? amperes.
Continuous
a continuous load is a load expected to continue for
According to the NEC, three (3) hours or more.The installation requirements
fixed outdoor deicing and for fixed outdoor electric deicing and snow melting
snow melting equipment is equipment, fixed outdoor electric deicing and snow
to be considered as a _____ melting equipment shall be considered a continuous
load. load.When sizing conductors and overcurrent
protection for the fixed outdoor equipment you must
take into consideration the equipment can operate
over 3 hours, so it is considered a continuous load.
All 15,20 amperes Ground fault circuit interceptor
receptacle outlets
installed in bathrooms of
dwelling units shall always
require
...........................................
, THHN
Conductors with _____
marked on the insulation conductors with THHN insulation are approved for
are NOT approved for use use in dry and damp locations only and conductors
in a wet location. with THWN, THHW, and THW insulation are
recognized for use in dry and wet locations.
A continuous load is load 3
where the maximum
current is expected to
continue for ............ hours
or more.
Flexible cards may not be To replace a fixed wiring of a structure
used in the following
locations ..........
For a 300 ampere 4 awg
electrical circuit, what is
the minimum size copper 4 AWG is the minimum size wire for a 300 ampere
equipment grounding circuit
conductor as per NEC?
For a building or structure Grounded
where the meter
enclosure is adjacent to The meter enclosure to be grounded by connection
the service disconnecting on the load side of the service disconnect where (1)
means, it is permitted to no ground-fault protection is installed, (2) the meter
ground the meter enclosure is adjacent to the service disconnecting
enclosure to the _____ means, and (3) the grounded service conductor is not
conductor on the load smaller than the size specified
side of the service
disconnect if ground-fault
protection is not provided.
and Answers
Save
Terms in this set (50)
A 440 volts motor has a 40 amperes
full load current of 34
amperes. what size The rating of disconnecting means is 115% of full load
disconnecting means is current.34 * 1.15 = 39.1 amperes.The nearer rating is 40
required? amperes.
Continuous
a continuous load is a load expected to continue for
According to the NEC, three (3) hours or more.The installation requirements
fixed outdoor deicing and for fixed outdoor electric deicing and snow melting
snow melting equipment is equipment, fixed outdoor electric deicing and snow
to be considered as a _____ melting equipment shall be considered a continuous
load. load.When sizing conductors and overcurrent
protection for the fixed outdoor equipment you must
take into consideration the equipment can operate
over 3 hours, so it is considered a continuous load.
All 15,20 amperes Ground fault circuit interceptor
receptacle outlets
installed in bathrooms of
dwelling units shall always
require
...........................................
, THHN
Conductors with _____
marked on the insulation conductors with THHN insulation are approved for
are NOT approved for use use in dry and damp locations only and conductors
in a wet location. with THWN, THHW, and THW insulation are
recognized for use in dry and wet locations.
A continuous load is load 3
where the maximum
current is expected to
continue for ............ hours
or more.
Flexible cards may not be To replace a fixed wiring of a structure
used in the following
locations ..........
For a 300 ampere 4 awg
electrical circuit, what is
the minimum size copper 4 AWG is the minimum size wire for a 300 ampere
equipment grounding circuit
conductor as per NEC?
For a building or structure Grounded
where the meter
enclosure is adjacent to The meter enclosure to be grounded by connection
the service disconnecting on the load side of the service disconnect where (1)
means, it is permitted to no ground-fault protection is installed, (2) the meter
ground the meter enclosure is adjacent to the service disconnecting
enclosure to the _____ means, and (3) the grounded service conductor is not
conductor on the load smaller than the size specified
side of the service
disconnect if ground-fault
protection is not provided.