QUESTIONS AND ANSWERS GRADED A+ 100% VERIFIED.
What is a purpose of a control valve ANS >>> Control Flow to
water-based fire protection system
The gauge on the quick opening device shall indicate _____ as
compared to the gauge on the system side of the dry pipe
valve? ANS >>> the same pressure
What type of test shall be provided when a valve is returned to
service to determine that the valve is open? ANS >>> Valve status
test
What is a fire service main? ANS >>> A pipe and its appurtenances
on private property/ Pipe between a source of water and the
base of the system riser
, Name the system that utilizes a plate through which a pass a
specific amount of foam concentrates at a specific pressure. ANS
>>> Orifice Plate Proportioning
During an inspection, which of the following would be identified
as a sprinkler which shall be replaced? ANS >>> Corrosion
What are the inspection requirements for hangers and seismic
braces installed in concealed spaces? ANS >>> Periodic inspection
is not required
Gauges shall be replaced every _____ or tested every _____ by
comparison with a calibrated gauge ANS >>> 5 years/ 5 years
Where air pressure supervision is connected to a constantly
attended location gauges shall be inspected ______? ANS >>>
Monthly
Sprinklers installed in areas that are inaccessible for safety
consideration, due to process operations ____ be ____ during
each scheduled shutdown? ANS >>> Shall/ Inspected