spacing for smoke detectors or manufactured specs -
|\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔rule of thumb - 30ft
|\ |\ |\ |\ |\ |\
manual pull station height - CORRECT ANSWERS ✔✔3-1/2
|\ |\ |\ |\ |\ |\ |\ |\
to 4-1/2 ft
|\ |\
secondary power must turn of within ? seconds on loss of
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
primary supply - CORRECT ANSWERS ✔✔10 seconds
|\ |\ |\ |\ |\ |\
manual pull stations must be mounted within ? feet of
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
exits on each floor and spaced up to ? - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔5 ft, 200 ft |\ |\ |\ |\
residential, secondary power supply time - CORRECT
|\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔24 hours in normal, 4 minutes of full alarm
|\ |\ |\ |\ |\ |\ |\ |\ |\
commercial, secondary power supply time - CORRECT
|\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔24 hours in normal, 5 minutes of full alarm
|\ |\ |\ |\ |\ |\ |\ |\ |\
, live voice, secondary power supply time - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔24 hours in normal, 15 minutes of full power
|\ |\ |\ |\ |\ |\ |\ |\ |\
audible device decibels, public - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\
✔✔75 db minimum or 15 above ambient
|\ |\ |\ |\ |\ |\
audible device decibels, private - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\
✔✔45 db or 15 db above ambient
|\ |\ |\ |\ |\ |\
smoke detector test frequency, functionality - CORRECT
|\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔annually |\
smoke detector test frequency, visual - CORRECT
|\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔semi-annually |\
smoke detector test frequency, sensitivity - CORRECT
|\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔at installation and every alternate year
|\ |\ |\ |\ |\ |\ |\
thereafter
smoke detectors, CAN or CANNOT, be supported by their
|\ |\ |\ |\ |\ |\ |\ |\ |\
circuit conductors - CORRECT ANSWERS ✔✔cannot
|\ |\ |\ |\ |\
acceptable to the AHJ (authority having jurisdiction) -
|\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔Approved |\ |\