What type of extinguisher would you use on a wood pallet fire?
Ans: Class A (A:@ 5.2.1)
What class of extinguisher is safe for use on electrical equipment?
Ans: Class C (A:@ 5.2.3)
What type of extinguisher would be used on a fire involving solvents
and flammable gases?
Ans: Class B (A:@ 5.2.2)
What is the maximum travel distance to an extinguisher for Class B?
Ans: 30 feet or 75 feet, depending on the occupancy hazard
How many AFFF or FFFP extinguishers of what capacity shall be used
to fulfill extra hazard requirements?
Ans: 3 extinguishers, of 1.6 gallon capacity (6.3.1.1.2)
All rights reserved © 2025/ 2026 |
, Page |2
Two AFFF or FFFP fire extinguishers of at least what capacity shall be
permitted to be used to fulfill ordinary hazard requirements?
Ans: 1.6 gallons (6 liters) (6.3.1.1.3)
What is the maximum travel distance of Class K extinguishers from the
hazard?
Ans: 30 feet (6.6.2)
How often shall pump tank water and pump tank calcium chloride-
based antifreeze types of fire extinguishers be recharged with new
chemicals or water, as applicable?
Ans: 12 months (7.8.2.1)
Wetting agent shall be replaced how often in stored-pressure
extinguishers?
Ans: 12 months (7.8.2.2)
Oil content shall not exceed what?
Ans: 10 ppm by weight (7.8.3.9.3)