TEST 2026 COMPLETE QUESTIONS AND
CORRECT ANSWERS
◉ If you fail the written test you will not be permitted to Retest for.
Answer: 90 days
◉ The following is an example of what type of Ceiling. Answer:
Stooped
◉ A bean is defined as a structural or non structural solid member which
could jacks down into the rooms base more than _____ and is located
more than _____ apart on center. Answer: Down more than4" and 3'
apart
◉ The following are examples of line type detection except. Answer:
ionization smoke detector
◉ He could tonight a circuit to which automatic or manual initiating
devices are connected where the signal received does not identify the
device operated is called?. Answer: A signaling line circuit
◉ Secondary power supplies are required to have sufficient power to
operate the fire alarm system in a non alarm condition for _______
,hours and then be capable of operating all notification devices for a
minimum of ______ minutes. Answer: 24 hours and 5 minutes
◉ Secondary power supplies for emergency voice evacuation systems
are required to have sufficient power to operate the system in a non
along condition for ______ hours and kin be capable of operating the
system during a fire or other emergency for a minimum of ______
minutes. Answer: 24 hours and 15 minutes under maximum load
◉ Secondary power supply shall automatically provide power to the
protected premises fire alarm system within _______ seconds when ever
primary power fails to provide minimum voltage required for proper
operation?. Answer: 10 seconds
◉ Cording to NFPA chapter 4, batteries shall be permanently marked
with what information?. Answer: Month and year of manufacture
◉ NFPA 72 "record of completion" is prepared:. Answer: upon
completion of installation at just acceptance test
◉ According to NFPA chapter 4, the control panel charging apparatus
shall be taken full of recharging batteries within _____ _____ after
batteries have been fully discharged?. Answer: 24 hours
, ◉ According to the fire code of New York City, smoke detectors may be
tested by the following methods except for:. Answer: Measured aerosol
smoke introduced into the detector
◉ What type of drawing typically shows correct conductor counts?.
Answer: Riser diagrams
◉ According to the fire code and fire rules, who is responsible for
preventing unnecessary and unwanted alarms?. Answer: Owner of a
promise or a part thereof
◉ I'll take you way and which according to NFPA chapter 4, a coded
alarm signal shall consist of not less than ______ complete rounds of the
number transmitted. Each round shall consist of not less than a ______
impulses. Answer: 3 rounds and 3 impulses
◉ According to the fire rules, who is responsible for making in trees in
the smoke detector maintenance log?. Answer: The fire safety director or
a person designated by building owners if no FSD
◉ According to NFPA chapter 4, installation Conductors shall be
monitored for integrity. The occurrence of a single open or single ground
fault condition shall be automatically indicated within ______ seconds.
Answer: 200 seconds