Medical Gas Questions 100% Correct Answers New Update Exam receivers for medical air shall be equipped with ____ relieve valves, automatic & manual drains, sight glass medical air filters shall be located immediately upstream of the___ final line regulator medical air compressors that are designed to separate the oil-containing section from the compression chamber shall be provided with a coalescing filter with a(n) element change indicator medical air receivers shall be provided with a ____to permit servicing three-valve bypass dryers, filter & regulators shall be at least duplexed. Under normal operation, airflow shall be divided equally through each device False medical air shall be sampled at a _____ NPS valved sample port downstream of the final line pressure regulator 1/4'' Area alarm panels for medical gas systems shall indicate when line pressure in the area being monitored increases or decreases by 20% Area alarm sensors for vital life support & critical care areas shall be located on which side of the zone valve box assemblies? Patient room side, outlet inlet side, downstream side